2013-01-23 14:04:16RESIDENTIAL RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- FLAT ROOF:
 A) FLAT ROOF ASSEMBLY ON PAGE 30 OF NOA 08-0410.09
 SUBMITTED CAN'T BE USED IN THIS BUILDING. THE DESIGN
 PRESSURES ARE TOO LOW TOO MEET THE DESIGN PRESSURES
 REQUIRED BY R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL FOR
 THE PERIMETER AND CORNER AREAS. GENERAL LIMITATION #9
 DOESN'T ALLOW NAIL ENHANCING. NEED TO SELECT AN
 APPROVED ASSEMBLY WITH GENERAL LIMITATION #7, WHICH
 ALLOWS NAIL ENHANCING BY MEANS OF RAS 117 CALCULATIONS.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION ON LAST PAGE OF NOA
 SUBMITTED. NEED CALCULATIONS TO MEET DESIGN PRESSURES
 REQUIRED BY SEC. R301.2.1.4.3.
  
 ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO TAKE INTO CONSIDERATION THAT THIS
 BUILDING IS LOCATED ON EXPOSURE "C". SEE SEC.
 R301.2.1.4.3.
  
 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9N-3 FOR THE ADHESIVE TO BE USED FOR THE CONCRETE TILE.
 SEE CONCRETE TILE NOA SUBMITTED FOR LISTED ADHESIVE.
  
 3- PROVIDE 2 COPIES OF EACH PRODUCT APPROVAL AS
 REQUIRED BY SEC.107.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712