| 2013-01-25 15:22:24 | BUILDING PLAN REVIEW |
| | REVISION: 13010548 |
| | PERMIT: 12100536 |
| | ADD: 222 LAKEVIEW AVE # 200 |
| | CONT: HOLT LEE |
| | TEL: (561)373-3902 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1.1AND FP1 INDICATE (3) NEW FRENCH DOORS AND |
| | SIDE LIGHTS WITH THE USE OF A WATER CURTAIN ON BOTH |
| | SIDES OF THE UNITS. 2010 FBC-B 404.6 EXCEPTION # 1 DOES |
| | ALLOW THE USE OF A WATER CURTAIN FOR THE FIXED GLASS |
| | SIDELIGHTS IF THERE ARE NO HORIZONTAL MULLIONS THAT |
| | WOULD INTERFERE WITH THE WETTING THE COMPLETE SURFACE |
| | OF THE GLASS. THE ELEVATIONS PROVIDED DO SHOW THE USE |
| | OF HORIZONTAL MULLIONS THAT DEVERTS THE WATER CURTAIN |
| | FROM COMPLETELY COVERING THE GLASS. |
| | THE SECOND ISSUE WITH THE NEW GLAZED FRENCH DOOR |
| | OPENINGS, THE PLANS DO NOT PROVIDE A RATING OF THE |
| | DOOR. A WATER CURTAIN ONLY WORKS FOR WINDOWS, NOT |
| | DOORS. ANY DOORS THROUGH THE REQUIRED 1-HOUR FIRE |
| | BARRIER WALL MUST BE 3/4 HOUR RATED IN ACCORDANCE WITH |
| | 2010 FBC-B TABLE 715.4. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |