2013-01-25 15:22:24BUILDING PLAN REVIEW
 REVISION: 13010548
 PERMIT: 12100536
 ADD: 222 LAKEVIEW AVE # 200
 CONT: HOLT LEE
 TEL: (561)373-3902
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A1.1AND FP1 INDICATE (3) NEW FRENCH DOORS AND
 SIDE LIGHTS WITH THE USE OF A WATER CURTAIN ON BOTH
 SIDES OF THE UNITS. 2010 FBC-B 404.6 EXCEPTION # 1 DOES
 ALLOW THE USE OF A WATER CURTAIN FOR THE FIXED GLASS
 SIDELIGHTS IF THERE ARE NO HORIZONTAL MULLIONS THAT
 WOULD INTERFERE WITH THE WETTING THE COMPLETE SURFACE
 OF THE GLASS. THE ELEVATIONS PROVIDED DO SHOW THE USE
 OF HORIZONTAL MULLIONS THAT DEVERTS THE WATER CURTAIN
 FROM COMPLETELY COVERING THE GLASS.
 THE SECOND ISSUE WITH THE NEW GLAZED FRENCH DOOR
 OPENINGS, THE PLANS DO NOT PROVIDE A RATING OF THE
 DOOR. A WATER CURTAIN ONLY WORKS FOR WINDOWS, NOT
 DOORS. ANY DOORS THROUGH THE REQUIRED 1-HOUR FIRE
 BARRIER WALL MUST BE 3/4 HOUR RATED IN ACCORDANCE WITH
 2010 FBC-B TABLE 715.4.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved