| Plan Review Notes For Permit 13010543 |
| Permit Number |
13010543 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-02-04 11:05:41 | RESIDENTIAL (R3) REVISION, MECHANICAL REVIEW COMMENTS. | | | CODE: 2007 FBC. | | | | | | 1- EQUIPMENT SIZE WAS CHANGED. PROVIDE NEW EQUIPMENT | | | SIZING CALCULATIONS AS REQUIRED BY SEC. 13-607.AB.1. | | | | | | 2- PROVIDE REVISED ENERGY CALCULATIONS TO MATCH NEW | | | EQUIPMENT SIZING CALCULATIONS. | | | ***NOTE: KEEP IN MIND THAT THIS PROJECT WAS PERMITTED | | | UNDER FBC 2007. USE CORRECT FORM. | | | | | | 3- PREVIOUS APPROVED ENERGY CALCULATIONS AND REVISED | | | A/C PLANS SHOWED 18 SEER. ARCHITECT LETTER SUBMITTED | | | SHOWS 13 SEER. ARCHITECT'S LETTER IS INCORRECT. | | | COORDINATE SEER REQUIRED WITH ITEM #1 AND 2 ABOVE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|