| Plan Review Notes For Permit 13010543 |
| Permit Number |
13010543 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-01-25 16:36:31 | RESIDENTIAL (R3) REVISION, MECHANICAL REVIEW COMMENTS. | | | CODE: 2007 FBC. | | | | | | 1- PREVIOUS APPROVED ENERGY CALCULATIONS AND REVISED | | | A/C PLANS SHOWED 18 SEER. ARCHITECT LETTER SUBMITTED | | | SHOWS 13 SEER. ARCHITECT'S LETTER IS INCORRECT. | | | COORDINATE SEER REQUIRED WITH ITEM #1 AND 2 ABOVE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|