| Plan Review Notes For Permit 13010540 |
| Permit Number |
13010540 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-01-30 14:35:56 | MECHANICAL PLANS DENIED | | | 1) PROVIDE INFORMATION ON THE SIZE FASTENERS USED TO | | | ANCHOR | | | PIPE STANDS AND UNISTRUT TO ROOF, TO MEET WIND | | | RESISTANCE | | | PER SECTION 301.12 1210 FBC (M) | | | 2) PROVIDE A DETAIL ON HOW THE CONDENSER IS ANCHORED TO | | | THE ROOF | | | PER SECTION 301.12 FBC (M) 2010 | | | 3) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEMS AND | | | SECTION 606.3 INSTALLATION 2010 FBC (M) | | | 4) REFER TO SECTION 606.4.1 SUPERVISION .2010 FBC (M) | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|