| 2013-01-22 11:38:48 | 13010507 | | | 3901 S. FLAGLER DR. #601 | | | INTERIOR KITCHEN AND BATH REMODEL | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | SHOW LOCATION OF THE ELECTRICAL PANEL WITH REQUIRED | | | SAFE WORKING CLEARANCES. NEC 110.26 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | INCLUDE THE SIZE OF THE BRANCH CIRCUIT, WIRING METHOD | | | AND LOCATION OF DISCONNECTS FOR NEW EQUIPMENT. FBC | | | 107.1 | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | | | NOTE: AN ELECTRIC PERMIT IS REQUIRED. | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|