Plan Review Notes
Plan Review Notes For Permit 13010507
Permit Number 13010507
Review Stop E
Sequence Number 1
Notes
Date Text
2013-01-22 11:38:4813010507
 3901 S. FLAGLER DR. #601
 INTERIOR KITCHEN AND BATH REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 SHOW LOCATION OF THE ELECTRICAL PANEL WITH REQUIRED
 SAFE WORKING CLEARANCES. NEC 110.26
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
 INCLUDE THE SIZE OF THE BRANCH CIRCUIT, WIRING METHOD
 AND LOCATION OF DISCONNECTS FOR NEW EQUIPMENT. FBC
 107.1
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NOTE: AN ELECTRIC PERMIT IS REQUIRED.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  