| 2013-04-22 13:28:11 | |
| | PERMIT: 13010504 |
| | ADD: 631 EVERNIA ST. |
| | CONT: KAUFMAN LYNN |
| | TEL: (561)361-6700 |
| | |
| | |
| | EVERNIA PLACE |
| | AFFORDABLE SENIOR HOUSING |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 3RD REVIEW |
| | APRIL 22/ 2013 |
| | ACTION: DENIED |
| | |
| | 4TH REVIEW APRIL 24/2013 |
| | |
| | 1) 3RD REVIEW IN PROCESS OF UNITY OF TITLE, ENGINEERING |
| | WILL NOTIFY ME ONCE THE UNITY OF TITLE HAS BEEN |
| | RECORDED. |
| | |
| | THE CIVIL PLAN C-2 APPEARS THAT THE LOTS ARE TO BE |
| | UNIFIED, A TITLE OF UNITY IS REQUIRED. UNITY OF TITLE. |
| | THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL |
| | BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM |
| | 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE |
| | COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY |
| | OF OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY |
| | LINE REQUIREMENTS MAY BE DEEMED NOT APPLICABLE. |
| | SEE WEBSITE FOR APPLICATION: |
| | HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| | "APPLICATION FOR UNITY OF TITLE" |
| | |
| | HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| | -38-UNITYOFTITLE3.PDF |
| | |
| | VINCENT J NOEL |
| | SURVEYOR/REAL ESTATE SUPERVISOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 494-1040 EXT: 1096 |
| | FAX: 494-1116 |
| | E-MAIL: [email protected] |
| | |
| | ********************************************* |
| | |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | |
| | 2) 3RD REQUEST! THIS BUILDING IS CONSIDERED A THRESHOLD |
| | BUILDING, (3) SETS OF PLANS, PRODUCT APPROVALS WILL |
| | REQUIRED, ONE SET FOR THE SPECIAL INSPECTOR, ONE FOR |
| | THE FIELD, AND A COPY WILL BE KEPT ELECTRONICALLY BY |
| | THE BUILDING DEPARTMENT, FOR OUR RECORDS. |
| | |
| | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 2A) 2ND REQUEST. 109.3.6.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL |
| | INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A |
| | WRITTEN STRUCTURAL INSPECTION PLAN PREPARED BY THE |
| | ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST |
| | BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| | ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| | DOCUMENTS. |
| | |
| | 2B) 3RD REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT |
| | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | |
| | 2C) COMPLIED. THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | 2D) 3RD REQUEST. 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| | THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| | PENETRATIONS, FOR WALLS AND CEILINGS. ALL TRADES THAT |
| | PENETRATE THE FIRE RATED SLAB WILL NEED TO USE ONE |
| | PRODUCT THAT IS TO BE SPECED OUT BY THE DESIGNER OF |
| | RECORD, SO ALL PENETRATIONS WILL REQUIRE THE |
| | ENGINEERING SHEETS FOR THAT SPECIFIC PRODUCT AND |
| | APPLICATION. |
| | |
| | 2E) A THRESHOLD PLAN REVIEW STOP WILL BE PUT ON THIS |
| | PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY |
| | THE CHIEF BUILDING INSPECTOR KEN CONRAD: |
| | |
| | PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE |
| | (561) 805-6700) FOR IN-PROGRESS INSPECTIONS FOR |
| | AUDITING OF JOBSITE INSPECTIONS. |
| | |
| | 2E)(1) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONCRETE |
| | RESTORATION. THIS MAY BE SUBMITTED TO KEN CONRAD BY |
| | E-MAIL. KEN CONRAD: [email protected] |
| | |
| | 2E)(2) 3RD REQUEST. FOR THE SPECIAL INSPECTOR PLEASE |
| | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED |
| | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 3) SOILS REPORT BY ARDAMEN 11/19/2012, & 12/27/2012. |
| | 2010 FBC-B 1803.2 SOILS INVESTIGATION ARE PROVIDED WILL |
| | REQUIRE A PEDS SIGNATURE SINCE THEY ARE SIGNED AND |
| | SEALED. |
| | |
| | 4-5) COMPLIED. |
| | |
| | 6) 3RD REQUEST 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| | DRAWING STAMP) BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 7) 2ND 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | CORNELL GAGARGE DOOR PLEASE CIRCLE WHICH TYPE OF DOOR |
| | IS TO BE INSTALLED AND ASSOCIATED PRESSURES. |
| | |
| | (B) WINDOWS/ MULLIONS PLEASE CIRCLE WHICH APPLICATIONS |
| | WILL BE USED FOR TYPE OF GLAZING SIZE OF WINDOW AND |
| | ASSOCIATED PRESSURES, PLEASE INDICATE IF STEEL |
| | RE-INFORCEMENT WILL BE REQUIRED FOR THE ASSOCIATED |
| | PRESSUES. |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES ROOFING MEMBRANE |
| | COVER SHEET IS ACTUALLY ROOFING INSULATION, NOT THE |
| | ROOFING MEMBRANE, NO PRODUCT APPROVAL WAS SUBMITTED FOR |
| | THE ROOF COVERING. |
| | METAL ROOFING PLEASE CIRCLE WHICH SUB-SYSTEM IS TO BE |
| | INSTALLED, AND IF ENHANCED FASTENING WILL BE ALLOWED |
| | SEE ALLOWED. NOTE ONLY THE COVER SHEET WAS UPLOADED, |
| | NEITHER THE EVALUATION REPORT WAS UPLOADED NOR THE |
| | INSTALATION INSTRUCTIONS. |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 8) 2COMPLIED. |
| | |
| | 9) SHEET LS-101: |
| | |
| | 9A-F) COMPLIED . |
| | |
| | |
| | 10) SHEET A-201: |
| | 10A-B) COMPLIED. |
| | . |
| | 10C) BUILDING PROVISO: TO BE SUPPLIED AS A LOW VOLTAGE |
| | PERMIT. PROVIDE COMPLIANCE WITH F] 915.1 GENERAL. |
| | EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN |
| | ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA FIRE |
| | PREVENTION CODE. |
| | |
| | 10D)(1) 3RD REQUEST. MACHINE ROOM-LESS ELEVATORS SHEET |
| | A-621. KONE ECOSPACE. WILL NEED MANUFACTURERS |
| | REQUIREMENTS FOR INSTALLATION. MAY STILL NEED TO |
| | INCORPORATE HOIST WAY VENTING REQUIREMENTS FOUND IN |
| | 2010 FBC-B 3004. |
| | |
| | 10D) (2) COMPLIED. PROVIDE COMPLIANCE WITH 3002.4 |
| | ELEVATOR CAR TO ACCOMMODATE AN AMBULANCE STRETCHER. |
| | |
| | 11) SHEET A202 TRASH CHUTE |
| | 11A)3RD REQUEST. SEMI COMPLIED, LS-103/ LS-104. THE |
| | NORTH STAIRWELL INDICATES THE TRASH CHUTE ACTUALLY |
| | PENETRATING THE 2 HOUR FIRE RATED STAIR ENCLOSURE. |
| | PLEASE REVIEW 2010 FBC-B 1022.4 PENETRATIONS INTO & |
| | THROUGH AN EXIT ENCLOSURE. PLEASE REVIEW THE |
| | REQUIREMENTS FOR TERMINATION ROOM 708.13.4 ALSO SEE |
| | 708.8. 708.8 DEALS WITH HOW THE TRASH CHUTE WILL |
| | PENETRATE THE 2 HOUR SHAFT.T . |
| | |
| | 11B) COMPLIED. |
| | |
| | 11C) COMPLIED. |
| | |
| | 11D) 4/24/13 COMPLIED. 4TH REVIEW. |
| | |
| | 11E) 3RD REQUEST. 4/24/2013 4TH REVIEW. SHEET A-601 |
| | DETAIL # 1 TRASH CHUTE SHAFT STOPS AT THE BOTTOM OF THE |
| | 2ND FLOOR, IT DOES NOT CONTINUE THROUGH TO THE 1ST |
| | FLOOR ALTHOUGH THE SHAFT DOES PENETRATE THE 2ND FLOOR |
| | ASSEMBLY AND 1ST FLOOR WALL. PLEASE SEE 708.11 |
| | ENCLOSURE AT THE BOTTOM . TRASH CHUTE DETAILS WERE |
| | UPLOADED AND DEPICT A 2 HR HEAT ACTIVATED ACCORDIAN |
| | FIRE DAMPER. PLEASE PROVIDE THE MANUFACTURERS |
| | INSTALATION INSTRUCTIONS THAT WILL THE DAMPER TO BE |
| | INSTALLED ON A 45 DEGREE ANGLE, IT IS DEPICTED IN THERE |
| | LITERATURE AS A HORIZONTAL APPLICATION. |
| | |
| | 11F) COMPLIED. |
| | |
| | 11G) 3RD REQUEST. 4TH REVIEW 4/24/13 2010 FBC-B |
| | 708.13.6. AUTOMATIC SPRINKLERS SYSTEM. AN APPROVED |
| | AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED IN |
| | ACCORDANCE WITH SECTION 903.2.11.2. F] 903.2.11.2 |
| | RUBBISH AND LINEN CHUTES.BUILDINGS WITH SHUTES GREATER |
| | THAN 3 STORIES SHALL HAVE ADDTIONAL HEADS AT |
| | ALTERNATING FLOORS. NEITHER THE TRASH CHUTE NOR FIRE |
| | SPRINKLER DRAWINGS HAVE ONLY ONE FIRE SPRINKLER HEAD AT |
| | THE 3RD FLOOR. |
| | 2010 FBC-B 903.2.11.2. AN AUTOMATIC SPRINKLER SYSTEM |
| | SHALL BE INSTALLED AT THE TOP OF RUBBISH AND LINEN |
| | CHUTES AND IN THEIR TERMINAL ROOMS. CHUTES EXTENDING |
| | THROUGH THREE OR MORE FLOORS SHALL HAVE ADDITIONAL |
| | SPRINKLER HEADS INSTALLED WITHIN SUCH CHUTES AT |
| | ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL BE ACCESSIBLE |
| | FOR SERVICING. PROVIDE DETAILS FOR THE SERVICING OF THE |
| | FIRE SPRINKLERS. |
| | |
| | 12) COMPLIED. |
| | |
| | 13) 2ND REQUEST. SHEET A450 DETAILS 1-3 HAVE GENERAL |
| | NOTES, A602, A609, A-620 AT DETAILS INDICATING SOLID |
| | SHEATHING THEN NOTES 1 & 2 THE SPECIFIC NOTE INDICATES |
| | THE USE OF DENSE-DECK. PLEASE BE AWARE OF PRESSURES |
| | FROM THE PRODUCT APPROVAL WILL BE FOR 3/4 INCH OR 5/8 |
| | CDX PLYWOOD NOT FOR DENSE DECK, IF PLYWOOD IS USED IT |
| | NEEDS TO BE FIRE RETARDENT TREATED PLYWOOD SEE 603.1.1. |
| | |
| | 4/24/13 NOTE HAVE BEEN CHANGED TO 5/8 INCH CDX PLYWOOD, |
| | NO MENTION OF FIRE RETARDENT TREATED PLYWOOD. |
| | |
| | 13) COMPLIED. |
| | |
| | 14A) COMPLIED. |
| | |
| | 15) COMPLIED. |
| | |
| | 16) COMPIED. |
| | |
| | 17) COMPLIED. |
| | |
| | 18A-B COMPLIED. |
| | |
| | 18C) 3RD REQUEST.4TH REVIEW 4/24/13/ PLEASE SHOW |
| | COMPLIANCE WITH 2010 FBC-B 1207.3 STRUCTURE BORNE |
| | SOUND, FLOOR CEILING ASSEMBLIES TO HAVE A INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50, (45 IF FIELD |
| | TESTED). THE PLANS DO NOT PROVIDE WHAT FLOOR FINISHES |
| | WILL OCCUR IN THTE TENANT SUITES NOR THE COMMON AREAS |
| | OR ELECTRICAL ROOMS ... |
| | |
| | 19) COMPLIED |
| | |
| | 20)COMPLIED. |
| | |
| | 21) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | |
| | *****INFORMATIONAL*****PLEASE!!!!!!!: WHEN RESUBMITTING |
| | PLANS PLEASE INDICATE THE REVISION & REMOVE & REPLACE |
| | ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING |
| | THE ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION |
| | OF THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |