| 2013-02-06 15:13:02 | 610 EVERNIA STREET |
| | PERMIT #13010504 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE ADDRESS PROVIDED ON THE PLANS (627 EVERNIA STREET) |
| | DOES NOT MATCH THE ADDRESS PROVIDED ON THE PERMIT |
| | APPLICATION (631 EVERNIA STREET). |
| | |
| | PROVIDE A FREESTANDING SIGN (IN FRONT OF THE FIRE |
| | DEPARTMENT CONNECTION) READING, "FIRE LANE - NO PARKING |
| | BY ORDER OF THE FIRE DEPARTMENT." SIGN SHALL BE 12" X |
| | 18" WITH A WHITE BACKGROUND AND RED LETTERS AND SHALL |
| | BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE BOTTOM OF |
| | THE SIGN. |
| | |
| | ALL CONSTRUCTION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. THE FIRE PROTECTION STANDPIPE SYSTEM SHALL |
| | BE EXTENDED TO EACH FLOOR AS EACH FLOOR IS CONSTRUCTED. |
| | PORTABLE FIRE EXTINGUISHERS SHALL BE LOCATED THROUGHOUT |
| | THE CONSTRUCTION AREA. SMOKING SHALL BE PROHIBITED |
| | EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL CONSTRUCTION |
| | AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE |
| | SMOKING IS PERMITTED OUTSIDE THE BUILDING, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION |
| | 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES |
| | SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE |
| | DESIGN OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. AFTER |
| | THE BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS |
| | CAN THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE |
| | ENGINEERED CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | PROVIDE AN AUTOMATIC CLASS I STANDPIPE SYSTEM |
| | THROUGHOUT THE BUILDING INCLUDING THE PARKING GARAGE. |
| | |
| | PER NFPA 101 SECTION 7.2.2.5.4 - STAIRWAY |
| | IDENTIFICATION: NEW ENCLOSED STAIRS SERVING THREE OR |
| | MORE STORIES AND EXISTING ENCLOSED STAIRS SERVING FIVE |
| | OR MORE STORIES SHALL COMPLY WITH 7.2.2.5 (A) THROUGH |
| | (L). |
| | (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE |
| | WITHIN THE ENCLOSURE AT EACH FLOOR LANDING. |
| | (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL. |
| | (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP |
| | AND BOTTOM OF THE STAIR ENCLOSURE. |
| | (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF |
| | THE STAIR ENCLOSURE. |
| | (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND |
| | THE DIRECTION TO, EXIT DISCHARGE. |
| | (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE |
| | APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A |
| | POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN |
| | OR CLOSED POSITION. |
| | (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE. |
| | (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE |
| | WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE |
| | WALL. |
| | (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED |
| | AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH |
| | LETTERING. |
| | (J) SIGNAGE THAT READS "NO ROOF ACCESS" AND IS LOCATED |
| | UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL |
| | DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS. |
| | LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH. |
| | (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE |
| | MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS. |
| | MEZZANINE LEVELS SHALL HAVE THE LETTER "M" OR OTHER |
| | APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR |
| | NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER "B" |
| | OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING |
| | THE FLOOR LEVEL NUMBER. |
| | (M) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF |
| | THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN |
| | IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS. |
| | |
| | PER NFPA 101 SECTION 7.2.2.5.4.2: WHEREVER AN ENCLOSED |
| | STAIR REQUIRES TRAVEL IN AN UPWARD DIRECTION TO REACH |
| | THE LEVEL OF EXIT DISCHARGE, SPECIAL SIGNS WITH |
| | DIRECTIONAL INDICATORS SHOWING THE DIRECTION TO THE |
| | LEVEL OF EXIT DISCHARGE SHALL BE PROVIDED AT EACH FLOOR |
| | LEVEL LANDING FROM WHICH UPWARD DIRECTION OF TRAVEL IS |
| | REQUIRED. |
| | |
| | SHEET LS100: UPDATE THE CODE LIST TO REFERENCE THE 2010 |
| | EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH |
| | CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 |
| | WITH FLORIDA AMENDMENTS. |
| | |
| | SHEET LS102: PROVIDE FLOOR PAINT (OR SIMILAR MARKINGS) |
| | LEADING FROM EAST STAIR ENCLOSURE TO REAR EXTERIOR EXIT |
| | STAIR. |
| | |
| | SHEET LS102: INDICATE THE FIRE RATING OF THE WALLS FOR |
| | THE FIRE PUMP ROOM AND THE TRASH COLLECTION ROOM. |
| | |
| | SHEET A202: TRASH CHUTE STAIR PENETRATIONS ARE NOT |
| | PERMITTED ON ANY LEVEL PER SECTION 7.1.3.2 (NFPA 101). |
| | |
| | SHEET A800: NONE OF THE DOOR NUMBERS (001A, 001B, 016A |
| | ETC.) CAN BE LOCATED IN THE DOOR SCHEDULE. |
| | |
| | SHEET A800: FIRE-RATED DOORS SHOULD BE EQUIPPED WITH |
| | FIRE EXIT HARDWARE IN LIEU OF THE SPECIFIED PANIC |
| | HARDWARE. |
| | |
| | SHEET P1.2: NO FLOOR DRAIN PROVIDED IN FIRE PUMP ROOM. |
| | |
| | SHEET MEP1.1: STAIR SHAFT PENETRATIONS SHALL BE LIMITED |
| | TO EQUIPMENT ESSENTIAL TO THE FUNCTION OF THE STAIR |
| | (SPRINKLERS, STANDPIPES, STAIR PRESSURIZATION DUCTS, |
| | ETC.) |
| | |
| | SHEET E2.1: EXIT SIGN NEEDS TO IDENTIFY EXIT IS THROUGH |
| | A SIDE-SWINGING DOOR NOT A ROLLING OVERHEAD DOOR. |
| | |
| | SHEET E2.2: OCCUPANTS SHOULD NOT BE DIRECTED TO EXIT |
| | THROUGH THE FITNESS CENTER. |
| | |
| | SHEET E2.2: PROVIDE EXTERIOR EXIT SIGNS IDENTIFYING THE |
| | EXTERIOR STAIRS AS EXITS. |
| | |
| | SHEET E2.2: PROVIDE LIGHTING AND EMERGENCY LIGHTING |
| | ALONG THE ENTIRE EXIT PATHS LEADING TO A PUBLIC WAY. |
| | |
| | ELECTRICAL: NO FIRE ALARM CONSTRUCTION DOCUMENTS COULD |
| | BE LOCATED. PROVIDE SPEAKER/STROBE NOTIFICATION |
| | APPLIANCES WITH VOICE ANNOUNCEMENTS AND MICROPHONE. |
| | PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE |
| | NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN |
| | THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE |
| | BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR. |
| | |
| | ELECTRICAL: PROVIDE PHASE 1 RECALL AND PHASE II |
| | FIREFIGHTER EMERGENCY OPERATIONS FOR ELEVATORS. PROVIDE |
| | SMOKE DETECTION IN ELEVATOR LOBBY AND MACHINE ROOM |
| | AREAS. ELEVATOR RECALL SHALL BE INTERFACED WITH FIRE |
| | ALARM SYSTEM. |
| | |
| | ELECTRICAL: PLANS DO NOT INDICATE THE METHOD (HEAT |
| | DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO SHUNT |
| | TRIP POWER TO THE ELEVATOR IN THE EVENT AN AUTOMATIC |
| | SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE ROOM. |
| | |
| | ELECTRICAL: PROVIDE TAMPER SWITCHES FOR SUPERVISING THE |
| | BACKFLOW PREVENTER IN THE OPEN POSITION. |
| | |