| Notes |
| Date |
Text |
| 2013-01-22 09:38:26 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | PROVIDE AN ELECTRIC SERVICE RISER PLAN SHOWING THE NEW | | | PANEL, MAIN BREAKER, GROUNDING, CONDUIT AND FEEDER. THE | | | MAIN DISCONNECT SHALL BE LOCATED AT THE POINT OF | | | SUPPLY. NEC 215.15, 230.70 | | | | | | ELECTRICAL REPAIR OF AN EXISTING STRUCTURE IS REQUIRED | | | TO INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|