| 2013-03-25 11:23:03 | 550 SOUTH ROSEMARY AVENUE - SUITE #160 |
| | PERMIT #13010420 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | DEMOLITION: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE |
| | DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE |
| | EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR |
| | MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING |
| | SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH |
| | REQUESTS MUST BE SUBMITTED IN WRITING (FAX: |
| | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | SHEET LS1.0: EXISTING REAR EXIT ACCESS CORRIDOR NEEDED |
| | SOME WORK DURING LAST ROUTINE FIRE INSPECTION. NEW AND |
| | EXISTING PENETRATIONS SHALL BE A APPROPRIATELY |
| | PROTECTED. PROVIDE PERMANENT SIGNAGE THROUGHOUT |
| | CORRIDOR INDICATING "EXIT CORRIDOR - NO STORAGE OR |
| | COMBUSTIBLES." |
| | |
| | REPEAT COMMENT - SHEET A1.0: ALL EXIT AND EXIT ACCESS |
| | DOORS TO BE EQUIPPED WITH PANIC OR FIRE EXIT HARDWARE |
| | INCLUDING EXISTING DOORS LOCATED IN THE REAR EXIT |
| | ACCESS CORRIDOR ALONG COLUMN LINE "E." DOOR #111 TO BE |
| | PROVIDED WITH PANIC HARDWARE AS WELL. |
| | |
| | NEW COMMENT - SHEET A1.0: MAIN ENTRY #100 AND MAIN |
| | ENTRY #119 DOORS TO BE EQUIPPED WITH PANIC HARDWARE. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |