| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | DEMOLITION: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE |
| | DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE |
| | EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR |
| | MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING |
| | SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH |
| | REQUESTS MUST BE SUBMITTED IN WRITING (FAX: |
| | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| | DOORS WITH EXIT SIGNS. |
| | |
| | SHEET LS1.0: EXISTING REAR EXIT ACCESS CORRIDOR NEEDED |
| | SOME WORK DURING LAST ROUTINE FIRE INSPECTION. NEW AND |
| | EXISTING PENETRATIONS SHALL BE A APPROPRIATELY |
| | PROTECTED. PROVIDE PERMANENT SIGNAGE THROUGHOUT |
| | CORRIDOR INDICATING ?EXIT CORRIDOR ? NO STORAGE OR |
| | COMBUSTIBLES.? |
| | |
| | SHEET LS1.0: PROVIDE HANDRAILS ON BOTH SIDES OF STAIRS |
| | AT KJ BOOTH #104 AND MB CONTROL #112. HANDRAILS SHALL |
| | BE LOCATED NOT LESS THAN 34 INCHES AND NOT MORE THAN 38 |
| | INCHES ABOVE THE SURFACE OF THE TREAD, MEASURED |
| | VERTICALLY TO THE TOP OF THE RAIL FROM THE LEADING EDGE |
| | OF THE TREAD. HANDRAIL ENDS SHALL BE RETURNED TO THE |
| | WALL OR FLOOR OR SHALL TERMINATE AT NEWEL POSTS. |
| | HANDRAIL CROSS SECTION SHALL HAVE A DIAMETER OF NOT |
| | LESS THAN 1.25 INCHES AND NOT MORE THAN 2 INCHES. |
| | |
| | SHEET A1.0: ALL EXIT AND EXIT ACCESS DOORS TO BE |
| | EQUIPPED WITH PANIC OR FIRE EXIT HARDWARE INCLUDING |
| | EXISTING DOORS LOCATED IN THE REAR EXIT ACCESS CORRIDOR |
| | ALONG COLUMN LINE ?E.? DOOR #111 TO BE PROVIDED WITH |
| | PANIC HARDWARE AS WELL. |
| | |
| | SHEET FA-1: PROVIDE SPEAKER/STROBE NOTIFICATION |
| | APPLIANCES AS NEW ASSEMBLY OCCUPANCIES WITH AN OCCUPANT |
| | LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE FIRE ALARM |
| | NOTIFICATION BY VISIBLE SIGNALS AND VOICE |
| | ANNOUNCEMENTS. PROVIDE FIRE ALARM MICROPHONE NEAR |
| | ANUNCIATOR PANEL. PROVIDE A PRE-RECORDED FIRE ALARM |
| | EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS |
| | BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT, |
| | AND EXIT THE BUILDING IMMEDIATELY. MUSIC SHALL SHUT |
| | DOWN UPON ACTIVATION OF FIRE ALARM SYSTEM TO ALLOW FIRE |
| | ALARM MESSAGE TO BE INTELLIGIBLE. |
| | |
| | SHEET FA-1: NO FIRE ALARM NOTIFICATION APPLIANCES |
| | LOCATED IN KITCHEN PREP AREA OR OUTDOOR DINING AREA |
| | #118. |
| | |
| | SHEET FA-1: APPEAR TO HAVE INSUFFICIENT NUMBER OF |
| | NOTIFICATION APPLIANCES NEAR MECHANICAL BULL AREA |
| | #113/BAR #2. |
| | |
| | SHEET FS-1: CONSTRUCTION DOCUMENTS ESTABLISH BEN ELLIS |
| | AS ENGINEER OF RECORD; THEREFORE, FIRE SPRINKLER SHOP |
| | DRAWINGS AND HYDRAULIC CALCULATIONS SHALL NOT BE SIGNED |
| | AND SEALED BY THE CONTRACTOR PER FLORIDA STATUTE 633. |
| | |
| | SHEET FS-2: PROVIDE SPRINKLER PROTECTION IN WALK-IN |
| | BEER COOLER #110. |
| | |