| 2013-01-22 09:39:10 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | 1. REVISE FLOOR PLAN TO INCLUDE ROOM DESIGNATIONS. |
| | THERE IS A NOTE ON SHEET A1 THAT EMERGENCY ESCAPE AND |
| | RESCUE OPENINGS (FOR SLEEPING ROOMS) TO COMPLY WITH FBC |
| | 1029 (SEE ALSO FBC R310). |
| | |
| | 2. REVISE FLOOR PLAN TO INCLUDE HORIZONTAL ROLLER |
| | CONFIGURATIONS AND SINGLE HUNG CONFIGURATIONS OR REVISE |
| | WINDOW SCHEDULE TO INCLUDE THIS INFORMATIN (**SLEEPING |
| | ROOMS ONLY**). FOR INSTANCE, SEE OPENING O. THE WINDOW |
| | WIDTH EXCEEDS MAX FOR AN XO WINDOW, SEE SHEET 4, BUT |
| | NOT CLEAR WHETHER AN XOX (DETAIL B OR C) WILL MEET |
| | MINIMUM EGRESS WIDTH. SEE ALSO SHEET 4 OF SINGLE HUNG |
| | PRODUCT APPROVAL. |
| | |
| | 3. A2, WINDOW BUCK DETAIL, SPECIFICATION PROPOSES A 1X3 |
| | BEVELED BUCK. THIS CONFLICTS WITH THE GRAPHIC AND FBC R |
| | 612.10.2.1 WHICH REQUIRES FULL SUPPORT OF THE WINDOW |
| | UNLESS OTHERWISE TESTED. |
| | |
| | 4. DELEGATED ENGINEERING TO BE REVIEWED BY ENGINEER OF |
| | RECORD, FS471, FAC61G15 (WINDOW DESIGN PRESSURE |
| | ENGINEERING AND FLOOR PLAN). |
| | |
| | 5. SEE FBC 2010 ENERGY CONSERVATION, TABLE 101.4.1. |
| | COMPONENTS BEING CHANGED ARE TO MEET THE REQUIREMENTS |
| | OF FBC 2010 ENERGY CONSERVATION CHAPTER 4 WHEN THE |
| | ESTIMATED COST EXCEEDS 30 PERCENT OF THE ASSESSED VALUE |
| | OF THE STRUCTURE. |
| | |
| | |