2013-03-20 09:13:442010 FBC
  
 DENIED BY BUILDING
  
 1) THE TWO STRUCTURAL SHEETS THAT WERE SUBMITTED HAVE
 COPIED SIGNATURES OF THE ENGINEER IN THE TITLE BLOCK.
 FAC 61G15-23.002 REQUIRES THE ENGINEER'S ORIGINAL WET
 SIGNATURE. SUBMIT SIGNED AND SEALED STRUCTURAL
 DRAWINGS.
  
 2) ON SHEET 2 OF THE STRUCTURAL DRAWINGS WALL SECTION 1
 SPECIFIES 1 X 8 T&G FOR THE ROOF SHEATHING. THIS IS NOT
 ACCEPTABLE FOR 36" RAFTER SPACING. FBCR TABLE R803.1
 REQUIRES 1-1/2" T & G FOR THIS SPAN. PLEASE CORRECT.
 NOTE: THE SPECIFIED FASTENERS WILL NEED TO BE REVISED
 FOR THE THICKER LUMBER SHEATHING.
  
 3) SPECIFY THE ROOF PITCH ON THE PLANS. FBCR905.7.2
 WOOD SHINGLES REQUIRE A MINIMUM 3/12 SLOPE AND 905.8.2
 WOOD SHAKES REQUIRE A MINIMUM 4/12 SLOPE.
  
 4) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 CASEMENT WINDOWS, FIXED GLASS WINDOWS AND BUILT-UP
 ROOFING, SPECIFIED ON THE PLANS, THAT HAVE BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD. DCA
 RULE 9N-3 AND CITY AMENDMENTS 107.3.4.1
  
 5) THE STRUCTURAL DRAWINGS SPECIFY THREADED RODS
 ATTACHING THE RAFTERS AND GABLE FRAMING MEMBERS.
 HOWEVER, THE DRAWINGS APPEAR TO SHOW LAG BOLTS OR LARGE
 SCREWS BECAUSE THEY DO NOT APPEAR TO EXTEND ALL THE WAY
 THROUGH THE LUMBER IN ORDER TO BE BOLTED TOGETHER.
 PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 AND FBC R301.1
  
 6) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED
 BY THE OWNER/AGENT. FBC ENERGY CONSERVATION SECTION
 405.4
  