| Plan Review Notes For Permit 13010383 |
| Permit Number |
13010383 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-01 12:12:20 | 13010383 | | | 3024 WASHINGTON ROAD | | | RESIDENTIAL ADDITION | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | | | | RECEPTACLES IN THE BREAKFAST ROOM SHALL BE SERVED FROM | | | ONE OR MORE 20 AMPERE BRANCH CIRCUITS. NEC 210.52 | | | (B)(1) | | | | | | BALCONIES, DECKS AND PORCHES SHALL HAVE AT LEAST ONE | | | GFCI PROTECTED RECEPTACLE OUTLET. NEC 210.52 (E)(3) | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|