| 2013-03-27 15:34:59 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ROOF COVERING. |
| | |
| | ***NOTE: PLANTATION ROOF TILE NOA 10-0804.15 SUBMITTED |
| | WAS SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE |
| | WEBSITE AND DOWNLOAD CURRENT NOA. |
| | |
| | B) SELF-ADHESIVE UNDERLAYMENT FOR NEW CONCRETE ROOF |
| | TILE AS SPECIFIED BY THE ENGINEER OF RECORD. |
| | |
| | ***NOTE: BORAL ROOF UNDERLAYMENTS FL14317-R1 SUBMITTED |
| | CAN'T BE USED IN THIS BUILDING. ACCORDING TO SEC. |
| | 5.5.2.1 OF THE FLORIDA PRODUCT APPROVAL SUBMITTED THE |
| | MAXIMUM DESIGN PRESSURE IS -45PSF. NEED PRODUCT |
| | APPROVAL THAT MEETS OR EXCEEDS DESIGN PRESSURES FOR |
| | ROOF PERIMETER AND CORNER AREAS. SEE PLANS FOR |
| | CALCULATED DESIGN PRESSURES THAT NEED TO BE MET. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL OF THE ABOVE PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| | TO FBC. |
| | |
| | 3- ENGINEER OF RECORD TO PROVIDE COMPLETE ROOF ASSEMBLY |
| | SPECIFICATIONS AS REQUIRED BY SEC. 107.2.1.2 CITY |
| | AMENDMENTS. SPECIFY ROOF TILE FASTENING METHOD. |
| | DRAWINGS SUBMITTED DON'T SPECIFY TILE FASTENING METHOD. |
| | |
| | 4- CLARIFY ROOF SHEATHING THICKNESS. ROOF SHEATHING |
| | NOTE ON SHEET A2.0 SPECIFIES 19/32" CDX PLYWOOD ROOF |
| | SHEATHING, WHILE, CROSS SECTIONS 1/A5.0 AND 2/A5.0 |
| | SPECIFIES 3/4" PLYWOOD SHEATHING. SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 5- ENGINEER OF RECORD TO SPECIFY ON PLANS ROOF |
| | VENTILATION AS REQUIRED BY SEC. R806. SPECIFY LOCATION |
| | AND SIZE. |
| | |
| | 6- TRUSS PACKAGE SUBMITTED NEED TO HAVE ENGINEER'S |
| | ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY SEC. |
| | 61G15-23.002 FLORIDA ADMINISTRATIVE CODE AND CHAPTER |
| | 471 FLORIDA STATUTE. |
| | ***NOTE: PROVIDE TRUSS PACKAGE WITH ENGINEER'S SEAL AND |
| | SIGNATURE TO THE BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | |