| 2013-02-04 17:30:02 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2010 |
| | FBC-RESIDENTIAL THIS BUILDING IS LOCATED ON EXPOSURE |
| | "D" NOT "B". REVISE DESIGN SPECIFICATIONS AND REVISE |
| | ALL THE DESIGN PRESSURES AS REQUIRED. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ROOF COVERING. (CONCRETE TILE ACCORDING TO PROPERTY |
| | APPRAISAL). |
| | B) CONCRETE TILE ADHESIVE IF USING IT FOR THE |
| | INSTALLATION OF TILE. SEE TILE PRODUCT APPROVAL FOR |
| | LISTED PRODUCTS. |
| | C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS/DETAILS. ***NOTE; PROVIDE ONLY THE PRODUCT |
| | APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| | CONNECTOR. |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| | |
| | 4- ENGINEER OF RECORD TO PROVIDE COMPLETE ROOF ASSEMBLY |
| | SPECIFICATIONS AS REQUIRED BY SEC. 107.2.1.2 CITY |
| | AMENDMENTS. SPECIFY ROOF TILE FASTENING METHOD AND THE |
| | DESIGN PRESSURES. |
| | |
| | 5- PROVIDE ROOF SHEATHING COMPLETE SPECIFICATIONS. |
| | SPECIFY WOOD TYPE, THICKNESS AND FASTENING AS REQUIRED |
| | BY SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL. ***NOTE: |
| | MIN. 8D RING SHANK NAILS ARE REQUIRED AND CORNER AREAS |
| | (4'-0" MIN.) REQUIRE NAILING AT 4"O.C. |
| | |
| | 6- SPECIFY ON PLANS CARBON MONOXIDE ALARMS AS REQUIRED |
| | BY SEC. R315 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 7- SPECIFY ON PLANS ROOF VENTILATION AS REQUIRED BY |
| | SEC. R806. |
| | |
| | 8- SPECIFY ON PLANS ATTIC ACCESS FOR NEW ROOF AREA AS |
| | REQUIRED BY SEC. R807. |
| | |
| | 9- ENGINEER OF RECORD TO PROVIDE AL THE INFORMATION ON |
| | THE DRAWINGS TITLE BLOCK AS REQUIRED BY SEC. |
| | 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE AND CHAPTER |
| | 471 FLORIDA STATUTE. |
| | |