| Plan Review Notes For Permit 13010327 |
| Permit Number |
13010327 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2013-04-17 15:08:26 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. SEE FBC TABLE 602 REGARDING FIRE RESISTANCE | | | REQUIREMENTS AND REVISE PLANS TO SHOW COMPLIANCE; BOTH | | | DISTANCE TO PROPERTY LINES AS WELL AS DISTANCE TO | | | ASSUMED PROPERTY LINE BETWEEN PROPOSED SHED AND | | | EXISTING BUILDING. INCLUDE ALL INFORMATION REQUIRED TO | | | SHOW CODE COMPLIANCE SUCH AS BUILDING TYPE (FBC CHAPTER | | | 6), AREA, OCCUPANCY CLASSIFICATION (FBC CHAPTER 3). | | | | | | PER CONVERSATION WITH CONTRACTOR, THIS WILL BE | | | REDLINED. | | | | | | 2. SEE FBC TABLE 602. TYPE IIB STRUCTURE, 5' FROM | | | PROPERTY LINE REQUIRES A 1 HOUR RATED WALL. THE DETAIL | | | PROVIDED IS FOR A NON BEARING WALL, EXPOSURE TO INSIDE | | | ONLY. FBC 705.5, RATED WALLS LESS THAN 10' FROM THE | | | PROPERTY LINE ARE TO BE RATED FROM BOTH INSIDE AND | | | OUTSIDE. | | | | | | |
|