| 2013-01-16 15:16:45 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE PLANS APPEAR TO SHOW TWO SEPARATE UNITS EACH |
| | WITH IT'S OWN KITCHEN. FBCR 302.3 REQUIRES ONE HOUR |
| | FIRE-RESISTANCE BETWEEN THE TWO UNITS. SHOW COMPLIANCE. |
| | |
| | 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE |
| | STRUCTURE. SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION |
| | SECTION 401.2. |
| | |
| | 3) THE MEAN ROOF HEIGHT FOR THE STRUCTURE IS 20 FEET |
| | PER THE PLANS. PLEASE INCREASE THE OPENING PRESSURES TO |
| | CORRESPOND WITH THE 20 FT MRH. FBCR 301.2.1 |
| | |
| | 4) SHOW COMPLIANCE WITH FBC R318.1 FOR TERMITE |
| | PROTECTION. |
| | |
| | 5) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE |
| | ICYNENE SPRAY FOAM INSULATION. FBCR316.3 |
| | |
| | 6) PROVIDE A DETAIL SHOWING HOW THE FLOOR ASSEMBLY |
| | ABOVE THE COVERED ENTRY WILL BE INSULATED. FBC ENERGY |
| | CONSERVATION AND CITY AMENDMENTS 107.2.1 |
| | |
| | 7) THE NOA NUMBERS LISTED IN THE WINDOW AND DOOR |
| | SCHEDULES ON SHEET A-1 DO NOT MATCH THE ONES ON THE |
| | PRODUCT APPROVALS THAT WERE SUBMITTED. PLEASE CORRECT. |
| | CITY AMENDMENTS 107.2.1 AND DCA RULE 9N-3 |
| | |
| | 8) SPECIFY HOW THE BASE OF THE 4 X 4 POSTS SUPPORTING |
| | THE BALCONY WILL BE ANCHORED TO THE CONCRETE |
| | FOUNDATION. FBCR 301.1 |
| | |
| | 9) SPECIFY HOW THE BALCONY IS ATTACHED TO THE |
| | STRUCTURE. CITY AMENDMENTS 107.2.1.3 |
| | |
| | 10) THE FRONT ELEVATION ON A-1 SPECIFIES A 6 X 6 POST |
| | AT THE BALCONY. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 |
| | |
| | 11) SHOW THAT THE SPIRAL STAIRS COMPLY WITH FBCR |
| | 311.7.9.1. |
| | |
| | 12) THE TYPICAL FRAME DETAIL ON A-1 APPEARS TO SHOW |
| | THAT THE END OF THE SHIPPING CONTAINERS WHERE THE DOORS |
| | HAVE BEEN REMOVED WILL BE FRAMED WITH 2 X 2 X 1/4" |
| | STEEL. PLEASE CLARIFY. ALSO CLARIFY HOW THESE WILL BE |
| | WELDED TO THE STRUCTURE AND HOW THE CORRUGATED STEEL |
| | SKIN WILL BE ATTACHED TO THE FRAMING. PLEASE BE |
| | SPECIFIC. CITY AMENDMENTS 107.2.1 |
| | |
| | 13) PROVIDE COMPLETE DETAILS OF THE FRAMING AT THE |
| | WINDOW AND DOOR OPENINGS AT RIGHT AND LEFT ELEVATIONS. |
| | FBCR 301.1 AND CITY AMENDMENTS 107.2.1 |
| | |
| | 14) INDICATE THE TYPE OF ROOF COVERING THAT WILL BE |
| | USED AND SUBMIT PRODUCT APPROVALS FOR IT. FBCR 903.1 |
| | |
| | 15) INDICATE HOW THE PLUMBING VENT ROOF PENETRATIONS |
| | THROUGH THE CORRUGATED STEEL WILL BE FLASHED. FBCR |
| | 903.2 |
| | |
| | 16) SHOW COMPLIANCE WITH FBCR 318.6 FOR REQUIRED |
| | GUTTERS AND DOWNSPOUTS ON BUILDINGS WITH EAVES WITH |
| | LESS THAN 6 INCH PROJECTIONS. |
| | |
| | 17) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | HARDI-PLANK SIDING AND THE COMPOSITE DECKING AS |
| | REQUIRED BY DCA RULE 9N-3. |
| | |
| | 18) PROVIDE A STRUCTURAL ANALYSIS THAT INDICATES THE |
| | UPPER STORAGE CONTAINER CAN BE CANTILEVERED AS |
| | INDICATED ON THE PLANS. CITY AMENDMENTS 107.2.1.3 |
| | |