| 2013-01-10 11:50:54 | *** PLANS SUBMITTED ARE LACKING MUCH NEEDED INFOMATION |
| | *** |
| | |
| | 1) SEE FBC/EXISTING 909.1 MECHANICAL REQUIREMENTS. |
| | WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF |
| | AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW |
| | OCCUPANCY IS SUBJECT TO DIFFERENT KITCHEN EXHAUST |
| | REQUIREMENTS OR TO INCREASED MECHANICAL VENTILATION |
| | REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, MECHANICAL, THE INTENT OF THE RESPECTIVE FLORIDA |
| | BUILDING CODE, MECHANICAL PROVISIONS SHALL BE COMPLIED |
| | WITH FOR THE NEW OCCUPANCY. |
| | |
| | 2) SEE 2010 FBC/ENERGY 503.2.1 CALCULATION OF HEATING |
| | AND COOLING LOADS. |
| | DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE |
| | PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR |
| | ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE |
| | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT |
| | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE |
| | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE |
| | SIZING CALCULATION SHALL BE SUBMITTED WITH THE |
| | APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND |
| | COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD |
| | REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY |
| | SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE |
| | WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT HANDBOOK. |
| | ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN |
| | APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE |
| | DESIGN PARAMETERS SPECIFIED IN CHAPTER 3. |
| | |
| | 3) PROVIDE OUTDOOR AIR CALCULATIONS AND OUTDOOR AIR, |
| | PER 2010 FBC/M 403.2 OUTDOOR AIR REQUIRED. |
| | THE MINIMUM OUTDOOR AIRFLOW RATE SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 403.3. VENTILATION SUPPLY |
| | SYSTEMS SHALL BE DESIGNED TO DELIVER THE REQUIRED RATE |
| | OF OUTDOOR AIRFLOW TO THE BREATHING ZONE WITHIN EACH |
| | OCCUPIABLE SPACE. |
| | |
| | 4) SHOW EXHAUST AIR REQUIREMENTS FOR BATHROOMS AND ANY |
| | OTHER SPACES THAT MAY REQUIRE IT, PER 2010 FBC/M 403.3 |
| | AND TABLE 403.3. |
| | |
| | 5) PROVIDE FOR SHUTOFF DAMPER CONTROLS. |
| | BOTH OUTDOOR AIR SUPPLY AND EXHAUST DUCTS SHALL BE |
| | EQUIPPED WITH DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN |
| | THE SYSTEMS OR SPACES SERVED ARE NOT IN USE, PER 2010 |
| | FBC/ENERGY 503.2.4.4. |
| | |
| | 6) PROVIDE FOR BALANCE RETURN AIR, PER 2010 FBC/M 601.4 |
| | BALANCED RETURN AIR. |
| | RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS |
| | ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS |
| | IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING |
| | SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS |
| | RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN |
| | PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH |
| | RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID |
| | UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED |
| | BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS |
| | CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL |
| | BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS. |
| | PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING |
| | SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5 |
| | PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER |
| | PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE. |
| | |
| | 7) PER 2010 FBC/M 606.1 CONTROLS REQUIRED. |
| | AIR DISTRIBUTION SYSTEMS SHALL BE EQUIPPED WITH SMOKE |
| | DETECTORS LISTED AND LABELED FOR INSTALLATION IN AIR |
| | DISTRIBUTION SYSTEMS, AS REQUIRED BY THIS SECTION. DUCT |
| | SMOKE DETECTORS SHALL COMPLY WITH UL 268A. OTHER SMOKE |
| | DETECTORS SHALL COMPLY WITH UL 268. |
| | |
| | 8) PER 2010 FBC/M 607.5 WHERE REQUIRED. |
| | FIRE DAMPERS, SMOKE DAMPERS AND COMBINATION FIRE/SMOKE |
| | DAMPERS SHALL BE PROVIDED AT THE LOCATIONS PRESCRIBED |
| | IN SECTIONS 607.5.1 THROUGH 607.5.7. WHERE AN ASSEMBLY |
| | IS REQUIRED TO HAVE BOTH FIRE DAMPERS AND SMOKE |
| | DAMPERS, COMBINATION FIRE/SMOKE DAMPERS OR A FIRE |
| | DAMPER AND SMOKE DAMPER SHALL BE REQUIRED. |
| | |
| | 2010 FBC/M 607.5.1 FIRE WALLS. |
| | DUCTS AND AIR TRANSFER OPENINGS PERMITTED IN FIRE WALLS |
| | IN ACCORDANCE WITH SECTION 706.11 OF THE FLORIDA |
| | BUILDING CODE, BUILDING SHALL BE PROTECTED WITH LISTED |
| | FIRE DAMPERS INSTALLED IN ACCORDANCE WITH THEIR |
| | LISTING. WALLS BETWEEN TENANT SEPARATION, COMMON |
| | SPACES, AND LEASE SPACES WILL MOST LIKELY BE FIRE |
| | RATED. |
| | |
| | MECHANICAL PLAN REVIEW BY: |
| | TOM GORDON (HY-BYRD INC.) (561) 805-6732 |