| Plan Review Notes For Permit 13010149 |
| Permit Number |
13010149 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-01-10 12:58:01 | 701 SOUTH OLIVE AVENUE - SUITE 108 & 111 | | | PERMIT #13010149 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO - SUBMIT REVISION***** | | | | | | THE DRAWING LAYER CONTAINING THE HYDRAULIC NODE | | | INFORMATION APPEARS TO BE FROZEN. SHOW THE HYDRAULIC | | | NODES SO THE HYDRAULIC CALCULATIONS CAN BE REVIEWED | | | APPROPRIATELY. | | | | | | FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND | | | END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE | | | PROTECTED FROM UPWARD MOVEMENT. INDICATE THE HANGER | | | TYPE OR METHOD TO BE USED FOR RESTRAINING UPWARD | | | MOVEMENT. | | | | | | INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE AND THE | | | HYDROSTATIC TEST PRESSURE ASSOCIATED WITH THIS FLOOR. | | | | | | THE EXTENDED COVERAGE PENDENT SPRINKLER (TY4232) | | | LOCATED IN OFFICE #207 HAS AN OPERATING TEMPERATURE OF | | | 155F MAKING THE SPRINKLER STANDARD RESPONSE ACCORDING | | | TO THE LISTING INFORMATION. THIS SPRINKLER WILL NEED AN | | | OPERATING TEMPERATURE OF 135F TO QUALIFY AS QUICK | | | RESPONSE. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|