 PERMIT #13010149
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 THE DRAWING LAYER CONTAINING THE HYDRAULIC NODE
 INFORMATION APPEARS TO BE FROZEN. SHOW THE HYDRAULIC
 NODES SO THE HYDRAULIC CALCULATIONS CAN BE REVIEWED
 APPROPRIATELY.
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. INDICATE THE HANGER
 TYPE OR METHOD TO BE USED FOR RESTRAINING UPWARD
 MOVEMENT.
  
 INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE AND THE
 HYDROSTATIC TEST PRESSURE ASSOCIATED WITH THIS FLOOR.
  
 THE EXTENDED COVERAGE PENDENT SPRINKLER (TY4232)
 LOCATED IN OFFICE #207 HAS AN OPERATING TEMPERATURE OF
 155F MAKING THE SPRINKLER STANDARD RESPONSE ACCORDING
 TO THE LISTING INFORMATION. THIS SPRINKLER WILL NEED AN
 OPERATING TEMPERATURE OF 135F TO QUALIFY AS QUICK
 RESPONSE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  