| Date |
Text |
| 2013-08-17 17:41:28 | 2119 SOUTH DIXIE HIGHWAY |
| | PERMIT #13010089 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET A-2: THE EXISTING HVAC ROOM IS INDICATED AS BEING |
| | A STORAGE ROOM. PER NFPA 1 SECTION 10.19.5.1, |
| | COMBUSTIBLE MATERIAL SHALL NOT BE STORED IN MECHANICAL |
| | ROOMS OR ELECTRICAL ROOMS. |
| | |
| | AS A NON-SEPARTED MIXED USE BUILDING, THE MOST STRIGENT |
| | LIFE SAFETY ITEMS PER OCCUPANCY WILL BE APPLICABLE. |
| | THEREFORE, PER NFPA 101 SECTION 38.3.4.1 A FIRE ALARM |
| | SYSTEM SHALL BE PROVIDED WHERE THE BUILDING IS THREE OR |
| | MORE STORIES IN HEIGHT. |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND FIRE ALARM SYSTEM. |
| | |
| | SPRINKLER DRAWINGS: DRAWINGS REQUIRE ENGINEER'S |
| | SIGN/SEAL. FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY |
| | AN APPROVED SUPERVISING STATION IN ACCORDANCE WITH NFPA |
| | 72. |
| | |
| | SPRINKLER DRAWINGS: INDICATE THE SYSTEM IMPROVEMENTS |
| | THAT WILL BE IMPLEMENTED TO BRING THE EXISTING PIPE |
| | SCHEDULE INTO COMPLIANCE WITH NFPA 13. NOTE: PER NFPA |
| | 25 SECTION 5.3.1.1.1, WHERE SPRINKLERS HAVE BEEN IN |
| | SERVICE FOR 50 YEARS, THEY SHALL BE REPLACED OR |
| | REPRESENTATIVE SAMPLES FROM ONE OR MORE SAMPLE AREAS |
| | SHALL BE TESTED. TEST PROCEDURES SHALL BE REPEATED AT |
| | 10-YEAR INTERVALS. WHERE REQUIRED BY THIS SECTION, |
| | SAMPLE SPRINKLERS SHALL BE SUBMITTED TO A RECOGNIZED |
| | TESTING LABORATORY ACCEPTABLE TO THE AUTHORITY HAVING |
| | JURISDICTION FOR FIELD SERVICE TESTING. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| 2013-08-07 16:14:47 | NEW SHEETS SUBMITTED. JG. |