| 2013-05-16 15:17:37 | 2119 SOUTH DIXIE HIGHWAY |
| | PERMIT #13010089 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL: HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE |
| | STAIR. HANDRAIL CROSS SECTION SHALL HAVE A DIAMETER OF |
| | NOT LESS THAN 1.25 INCHES AND NOT MORE THAN 2 INCHES. |
| | |
| | SHEET LS-1: STAIR ENCLOSURE DOOR #10 OBSTRUCTS THE |
| | EGRESS PATH OF OCCUPANTS UTILIZING DOOR #11. |
| | |
| | SHEET A-4: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE |
| | BUILDING ADDRESS VISIBLE FROM THE STREET ON EAST |
| | ELEVATION. NUMBERS SHALL BE ATTACHED TO THE BUILDING |
| | AND BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE |
| | AND SHALL CONTRAST THE BACKGROUND. |
| | |
| | SPRINKLER DRAWINGS: DRAWINGS REQUIRE ENGINEER'S |
| | SIGN/SEAL. FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY |
| | AN APPROVED SUPERVISING STATION IN ACCORDANCE WITH NFPA |
| | 72. |
| | |
| | SPRINKLER DRAWINGS: INDICATE THE SYSTEM IMPROVEMENTS |
| | THAT WILL BE IMPLEMENTED TO BRING THE EXISTING PIPE |
| | SCHEDULE INTO COMPLIANCE WITH NFPA 13. NOTE: PER NFPA |
| | 25 SECTION 5.3.1.1.1, WHERE SPRINKLERS HAVE BEEN IN |
| | SERVICE FOR 50 YEARS, THEY SHALL BE REPLACED OR |
| | REPRESENTATIVE SAMPLES FROM ONE OR MORE SAMPLE AREAS |
| | SHALL BE TESTED. TEST PROCEDURES SHALL BE REPEATED AT |
| | 10-YEAR INTERVALS. WHERE REQUIRED BY THIS SECTION, |
| | SAMPLE SPRINKLERS SHALL BE SUBMITTED TO A RECOGNIZED |
| | TESTING LABORATORY ACCEPTABLE TO THE AUTHORITY HAVING |
| | JURISDICTION FOR FIELD SERVICE TESTING. |
| | |
| | ELECTRICAL DRAWINGS: PROVIDE ENGINEERED LAYOUT OF |
| | ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING. |
| | EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM |
| | OF 1-1/2 HOURS IN THE EVENT OF FAILURE OF NORMAL |
| | LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE |
| | ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT |
| | LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, |
| | NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF |
| | EGRESS AT FLOOR LEVEL. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |