| 2013-07-10 13:54:24 | CHECK VALUE. $20,000 TO DO A CHANGE OF |
| | USE FROM CAR DEALER TO RESTAURANT????. |
| | ELECTRICAL CONTRACTOR SUBMITTED |
| | SUBPERMIT APPLICATION 13070339 WITH A |
| | VALUE OF $20,000 JUST TO DO THE SERVICE |
| | CHANGE.???? JG. |
| | |
| | |
| | |
| 2013-05-21 15:26:47 | BUILDING PLAN REVIEW |
| | PERMIT: 13010089 |
| | ADD: 2119 S DIXIE HWY |
| | CONT: SOUTHEAST CONSTRUCTION. |
| | TEL: (954)394-3991 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | MAY 31/2013 |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) SHEET SP-1 THE DESIGNER OF RECORD HAS ELECTED TO USE |
| | 2010 EXISTING BUILDING CODE 912.1.1.2 CHANGE OF |
| | OCCUPANCY CLASSIFICATION WITH SEPARATION. THE FIRST |
| | FLOOR THERE IS NO SEPERATION BETWEEN THE A2 RESTARAUNT |
| | AND THE MERCANTILE OCCUPANCIES, THEN THE DESIGNER DOES |
| | PROVIDE SERERATION BETWEEN THE A2 ASSEMBLY AND BUSINESS |
| | OCCUPANCIES. |
| | |
| | 3) COMPLIED. |
| | |
| | 4A) 2ND REQUEST. SHEET SP-1, OCCUPANT LOAD CHART, FIRST |
| | FLOOR THE RETAIL LOUNGE, RETAIL BOUTIQUE & COFFEE SHOP |
| | ALL LIST 60 SQ FT PER OCCUPANT PLEASE REVIEW 2010 FBC-B |
| | TABLE 1004.1.1 FOR MERCANTILE GRADE FLOOR AT 30 SQ FT/ |
| | OCCUPANT. |
| | |
| | 4B) COMPLIED. KITCHEN WILL COME IN UNDER SEPERATE |
| | PERMIT. |
| | |
| | 5) SHEET SP-1 LIFE SAFETY PLAN, PLEASE PROVIDE THE |
| | FURNATURE LAYOUT FOR MEANS OF EGRESS, ACCESSIBLE PATH |
| | OF TRAVEL ... EXST BLDG CODE 905.1. |
| | |
| | 6) COMPLIED. |
| | |
| | 7A) 2ND REQUEST, SHEET SP-1 FREIGHT ELEVATOR. THE |
| | DESIGNER OF RECORD HAS NOT INDICATED THE EXISTING |
| | ELEVATOR WALLS ARE CREATING A RATED SHAFT, NOTED THE |
| | PLANS INDICATE THE USE OF FIRE SHUTTERS OVER THE |
| | OPENINGS. IN THE LAST MEETING THE FIRST FLOOR FIRE |
| | SHUTTER WAS GOING TO BE REMOVED IN CASE OF FIRE IF THIS |
| | ELEVATOR WAS GOING TO BE USED THEY COULD STILL GET OUT |
| | OF THE FREIGHT ELEVATOR.ITS THE SAME IDEA AS THE |
| | REQUIRED ELEVATOR LOBBY THAT WOULD STILL HAVE ONE MEANS |
| | OF EGRESS 708.14.1 WHEN THE FREIGHT ELEVATOR RETURNS TO |
| | THE FIRST FLOOR.. |
| | |
| | 2010 EXISTING BUILDING CODE IN EITHER CASE IF THE |
| | DESIGNER OF RECORD CHOICES 912.1.1.1 OR 912.1.1.2 |
| | SEPERATED OR NON-SEPERATED USE BOTH CODE SECTIONS REFER |
| | YOU BACK TO CHAPTER 8 FOR THE NEW OCCUPANCY |
| | CLASSIFICATION IN THE BUILDING AND THE REQUIREMENTS OF |
| | THIS CHAPTER. THE PROVISIONS ESSENTIALLY CLASSIFY |
| | CHANGES OF OCCUPANCY CLASSIFICATION AS LEVEL 3 |
| | ALTERATIONS. BY DIRECTLY STATING THE REQUIEMENTS OF |
| | CHAPTER 8 SHALL OVERRIDES THE REQUIREMENT FOR THE |
| | RECONFIGURATION OR ALTERATION TO BE OCCURRING IN THE 50 |
| | PER CENT OR MORE OF THE TOTAL BUILDING. THE APPLICATION |
| | OF CHAPTER 8 IN TURN REQUIRES COMPLIANCE WITH CHAPTERS |
| | 6 & 7 AS STATED IN SECTION 801.2. |
| | 2010 EXST BLDG CODE 703.2.1 EXISTING VERTICAL OPENINGS. |
| | ALL EXISTING INTERIOR VERTICAL OPENINGS CONNECTING TWO |
| | OR MORE FLOORS SHALL COMPLY WITH THE APPROPRIATE |
| | SECTIONS OF THE FLORIDA FIRE PREVENTION CODE. |
| | 2010 EXST BLDG CODE 912.7 ENCLOSURE OF VERTICAL SHAFTS. |
| | ENCLOSURE OF VERTICAL SHAFTS SHALL BE IN ACCORDANCE |
| | WITH SECTIONS 912.7.1 THROUGH 912.7.4. |
| | 2010 EXST BLDG CODE 912.7.3 OTHER VERTICAL SHAFTS. |
| | INTERIOR VERTICAL SHAFTS OTHER THAN STAIRWAYS, |
| | INCLUDING BUT NOT LIMITED TO ELEVATOR HOISTWAYS AND |
| | SERVICE AND UTILITY SHAFTS, SHALL BE ENCLOSED AS |
| | REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING WHEN |
| | THERE IS A CHANGE OF USE TO A HIGHER HAZARD CATEGORY AS |
| | SPECIFIED IN TABLE 912.4. |
| | |
| | 2010 EXST BLDG CODE 912.7.4 OPENINGS. ALL OPENINGS INTO |
| | EXISTING VERTICAL SHAFT ENCLOSURES SHALL BE PROTECTED |
| | BY FIRE ASSEMBLIES HAVING A FIRE-PROTECTION RATING OF |
| | NOT LESS THAN 1 HOUR AND SHALL BE MAINTAINED |
| | SELF-CLOSING OR SHALL BE AUTOMATIC CLOSING BY ACTUATION |
| | OF A SMOKE DETECTOR. ALL OTHER OPENINGS SHALL BE FIRE |
| | PROTECTED IN AN APPROVED MANNER. EXISTING FUSIBLE |
| | LINK-TYPE AUTOMATIC DOOR-CLOSING DEVICES SHALL BE |
| | PERMITTED IN ALL SHAFTS EXCEPT STAIRWAYS IF THE FUSIBLE |
| | LINK RATING DOES NOT EXCEED 135?F (57?C). |
| | |
| | 7B) SHEET LS-2 THE NORTHWEST STAIRWELLDOES NOT INDICATE |
| | THIS IS A FIRE RATED WALL. EXST BLDG CODE 703.2.3 |
| | SUPPLEMENTAL STAIRWAY ENCLOSURE REQUIREMENTS. WHERE THE |
| | WORK AREA ON ANY FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR |
| | AREA, STAIRWAYS THAT ARE PART OF THE MEANS OF EGRESS |
| | SERVING THE WORK AREA SHALL, AT A MINIMUM, BE ENCLOSED |
| | WITH SMOKE-TIGHT CONSTRUCTION ON THE HIGHEST WORK AREA |
| | FLOOR AND ALL FLOORS BELOW. |
| | EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY |
| | THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE |
| | PREVENTION CODE. |
| | |
| | 2010 EXST BLDG CODE 912.7.2 STAIRWAYS. WHEN A CHANGE OF |
| | OCCUPANCY CLASSIFICIATION IS MADE TO A HIGHER HAZARD |
| | CATEGORY AS SHOWN IN TABLE 912.4, INTERIOR STAIRWAYS |
| | SHALL BE ENCLOSED AS REQUIRED BY THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 7C) DOORS THAT ARE REQUIRED TO BE RATED FOR STAIRWELLS, |
| | VERTICAL LULA LIFTS FOR THE 2ND & 3RD FLOOR ARE NOT |
| | LOCATED ON THE DOOR SHCEDULE FOUND ON SHEET A6. 2010 |
| | FBC-B OPENING PROTECTIVES, TABLE 715.4. |
| | |
| | 8) SECTION 904 FIRE PROTECTION 904.1 GENERAL. FIRE |
| | PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY |
| | WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE |
| | OF OCCUPANCY CLASSIFICATION. NO FIRE SPRINKLER PLANS |
| | WERE SUBMITTED, THE COVER SHEET INDICATES THIS TO BE A |
| | FULLY SPRINKLERED BUILDING. |
| | |
| | 9) SECTION 905 MEANS OF EGRESS. 905.1 GENERAL. |
| | MEANS OF EGRESS IN PORTIONS OF BUILDINGS UNDERGOING A |
| | CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH |
| | SECTION 912. |
| | EXST BLDG CODE912.4.1 MEANS OF EGRESS FOR CHANGE TO |
| | HIGHER HAZARD CATEGORY. |
| | WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A |
| | HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE |
| | 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | THE STAIRWELLS WILL NEED TO PROVIDE HANRAILS ON BOTH |
| | SIDES OF THE STAIRS IN COMPLIANCE WITH 1012.1-9 & |
| | GAURDRAILS WHEN THERE IS NO WALLS INCOMPLIANCE WITH |
| | 1013.1-3. |
| | |
| | 10) PLEASE PROVIDE THE MANUFACTURERS SPEC FOR THE LULA |
| | LIFT INDICATING COMPLIANCE WITH 2010 ACCESSIBILITY CODE |
| | 410.1 ASME A18.1. 2010 EXST BLDG CODE SECTION 906 |
| | ACCESSIBILITY 906.1 ACCESSIBILITY IN PORTIONS OF |
| | BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE |
| | FLORIDA BUILDING CODE, ACCESSIBILITY. |
| | 2010 EXST BLDG CODE 912.8 ACCESSIBILITY. EXISTING |
| | BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE |
| | FLORIDA BUILDING CODE, ACCESSIBILITY. |
| | |
| | 2010 ACCESSIBILTY CODE (FL GRAY BOX) 201.1.1 VERTICAL |
| | ACCESSIBILITY. |
| | SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS |
| | FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY |
| | BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE |
| | SECTIONS FROM THE DUTY TO PROVIDE VERTICAL |
| | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE |
| | OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE |
| | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH |
| | BUILDING, STRUCTURE OR FACILITY, EXCEPT FOR: |
| | SEE EXCEPTIONS. |
| | BUILDINGS, STRUCTURES AND FACILITIES MUST, AT A |
| | MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE ADA |
| | STANDARDS FOR ACCESSIBLE DESIGN. |
| | |
| | 2010 ACCESSIBILITY CODE.202.4 ALTERATIONS AFFECTING |
| | PRIMARY FUNCTION AREAS. |
| | IN ADDITION TO THE REQUIREMENTS OF 202.3, AN ALTERATION |
| | THAT AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS |
| | TO AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE |
| | SO AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE, |
| | THE PATH OF TRAVEL TO THE ALTERED AREA, INCLUDING THE |
| | REST ROOMS, TELEPHONES, AND DRINKING FOUNTAINS SERVING |
| | THE ALTERED AREA, ARE READILY ACCESSIBLE TO AND USABLE |
| | BY INDIVIDUALS WITH DISABILITIES, UNLESS SUCH |
| | ALTERATIONS ARE DISPROPORTIONATE TO THE OVERALL |
| | ALTERATIONS IN TERMS OF COST PURSUANT TO 202.4.1. |
| | ALTERATIONS TO WINDOWS, HARDWARE, CONTROLS, ELECTRICAL |
| | OUTLETS, AND SIGNAGE SHALL NOT BE DEEMED TO BE |
| | ALTERATIONS THAT AFFECT THE USABILITY OF OR ACCESS TO |
| | AN AREA CONTAINING A PRIMARY FUNCTION. |
| | |
| | 202.4.1 DISPROPORTIONATE COST. |
| | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | |
| | 11) LS-3 THE SOUTH STAIRWELL INDICATES THE LULA LIFT |
| | WITHIN THE NEW STAIR ENCLOSURE. 2010 FBC-B 1022.4 |
| | REQUIRED PENETRATIONS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |