| 2013-01-14 14:20:14 | 2119 SOUTH DIXIE HIGHWAY |
| | PERMIT #13010089 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | OTHER THAN THE COVER SHEET, THE PROJECT ADDRESS IS |
| | INCORRECTLY INDICATED AS 2199 SOUTH DIXIE HIGHWAY. |
| | |
| | PROVIDE A LIFE SAFETY PLANS INDICATING FURNITURE |
| | LAYOUTS, NEW/EXISTING HOURLY FIRE BARRIER RATINGS, |
| | EMERGENCY LIGHTING, COMMON PATH OF TRAVEL ETC. |
| | |
| | EXIT DISCHARGE,STAIRS AND EGRESS COMPONENTS SHALL |
| | CONFORM TO THE LIFE SAFETY REQUIREMENTS OF CHAPTER 7 OF |
| | NFPA 101 FLORIDA 2007 EDITION. TOO MANY VIOLATIONS TO |
| | LIST. |
| | |
| | OCCUPANT LOAD FACTORS SHALL COMPLY WITH TABLE 7.3.1.2 |
| | OF THE FFPC. SEVERAL OCCUPANT LOAD FACTORS ARE |
| | INCORRECT SUCH AS 60 SQ.FT. PER PERSON FOR MERCANTILE |
| | ON STREET FLOOR. A CONFERENCE ROOM WOULD BE FIGURED AT |
| | 15 SQ.FT. PER PERSON AS THE USAGE IS ASSEMBLY. |
| | |
| | THE SECOND FLOOR INDICATES WORK TABLES; PLEASE INDICATE |
| | HOW THIS SPACE WILL BE USED. |
| | |
| | THE THIRD FLOOR INDICATES SEVERAL DISPLAY CASES SO A |
| | STORAGE OCCUPANCY IS NOT APPROPRIATE FOR THIS USAGE. |
| | |
| | HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR. |
| | HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND |
| | NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD, |
| | MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE |
| | LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE |
| | RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT |
| | NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A |
| | DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN |
| | 2 INCHES. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA |
| | FIRE PREVENTION CODE ? NFPA 101 |
| | |
| | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. REFERENCE |
| | SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION CODE ? NFPA |
| | 101 |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING |
| | SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR |
| | AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL |
| | HAVE "NO SMOKING" SIGNS POSTED. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND |
| | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| | 500 NORTH DIXIE HIGHWAY. |
| | |
| | ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE |
| | REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE |
| | BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN |
| | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED |
| | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA |
| | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED |
| | SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. |
| | |
| | TOO MANY CODE VIOLATIONS EXIST ON THE PLANS AT THIS |
| | TIME TO PERFORM A THOROUGH AND COMPLETE PLAN REVIEW. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |