| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. |
| | |
| | INDICATE THE FAULT CURRENT CAPABILITY OF THE SERVICE |
| | EQUIPMENT AND PANEL BOARDS. VERIFY THE EQUIPMENT FAULT |
| | CURRENT RATING IS SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE |
| | FOR THE CURRENT THAT MUST BE INTERRUPTED. NEC 110.9 |
| | |
| | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| | SERVICE GROUND. NEC 250.94 |
| | |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH |
| | PROTECTION, HIGH-LEG MARKING, AND THE ELECTRICAL |
| | SERVICE EQUIPMENT AND DISCONNECTING MEANS. |
| | NEC 110.22, 110.16, 110.22 |
| | |
| | PROVIDE PANEL BOARD SCHEDULES SHOWING BALANCED LOADS. |
| | INCLUDE A SUMMARY LOAD CALCULATION FOR THE SERVICE |
| | EQUIPMENT. NEC 210.3, 215.2, 220.40, 408.4 |
| | |
| | VERIFY SAFETY CLEARANCES HAVE BEEN OBSERVED FOR PANEL |
| | ?C?. NEC 215.5, 110.26 |
| | |
| | PROVIDE DEDICATED 20 AMPERE BRANCH CIRCUIT (S) FOR |
| | SIGNAGE. NEC 600.5 |
| | |
| | RECEPTACLE OUTLETS ARE REQUIRED FOR SHOW WINDOWS. NEC |
| | 210.62, 220.14, 220.40, 220.43 |
| | |
| | GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS. |
| | NEC 422.52 |
| | |
| | ALL RECEPTACLES LOCATED WITHIN SIX FEET OF SINKS MUST |
| | BE GFCI PROTECTED. NEC 210.8 |
| | |
| | PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE |
| | WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC |
| | ENERGY CONSERVATION 505.3 |
| | |
| | NOTE: |
| | SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE, |
| | DATA, FIRE ALARM, SECURITY, SIGNAGE, AND SITE LIGHTING. |
| | |