2013-01-07 14:41:132010 FBC
  
 DENIED BY PLUMBING
  
 1) NOT MORE THAN 0NE WET VENTED FIXTURE DRAIN SHALL
 DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN
 CONNECTION PER FBCR P3108.2.1 AND FBCR P3108.1 REQUIRES
 EACH WET VENTED FIXTURE DRAIN TO CONNECT INDEPENDENTLY
 TO THE HORIZONTAL WET VENT. SEE TUB AND WATER CLOSET AT
 MASTER BATH.
  