| Plan Review Notes For Permit 13010059 |
| Permit Number |
13010059 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-01-07 14:41:13 | 2010 FBC | | | | | | DENIED BY PLUMBING | | | | | | 1) NOT MORE THAN 0NE WET VENTED FIXTURE DRAIN SHALL | | | DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN | | | CONNECTION PER FBCR P3108.2.1 AND FBCR P3108.1 REQUIRES | | | EACH WET VENTED FIXTURE DRAIN TO CONNECT INDEPENDENTLY | | | TO THE HORIZONTAL WET VENT. SEE TUB AND WATER CLOSET AT | | | MASTER BATH. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|