Plan Review Notes
Plan Review Notes For Permit 13010059
Permit Number 13010059
Review Stop B
Sequence Number 1
Notes
Date Text
2013-01-07 16:20:332010 FBC
  
 DENIED BY BUILDING
  
 1) SPECIFY THE DESIGN WIND SPEED FOR THE STRUCTURE ON
 THE PLANS WITH THE DESIGN CRITERIA ON SHEET A-2. FBCR
 301.2.1
  
 2) BASED ON FBCR 301.2.1.4.3 THE STRUCTURE IS LOCATED
 IN EXPOSURE CATEGORY C NOT B. PLEASE REVISE.
  
 3) PROVIDE A FLOOR PLAN OF THE EXISTING STRUCTURE PRIOR
 TO THE REMODEL. CITY AMENDMENTS 107.2.1
  
 4) SPECIFY THE EXISTING AREA CALCULATIONS AND THE
 PROPOSED AREA CALCULATIONS ON THE PLANS. CITY
 AMENDMENTS 107.2.1.3
  
 5) NOTE: THE PLANS WILL BE REQUIRED TO BE REVIEWED BY
 PALM BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES ARE
 DUE.
  
 6) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE ADDED
 LIVING SPACE. FBC ENERGY CONSERVATION 401.2
  
 7) SPECIFY THE HORIZONTAL REINFORCEMENT FOR THE
 CONCRETE BOND BEAM AT THE TOP OF THE STEM WALL. FBCR
 404.1.1.1.1
  
 8) SHOW COMPLIANCE WITH FBCR 806.1 FOR ATTIC
 VENTILATION ON THE PLANS.
  
 9) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE NEW
 EXTERIOR DOORS, WINDOWS, STORM PANELS AS REQUIRED BY
 DCA RULE 9N-3.
  