| Plan Review Notes For Permit 13010059 |
| Permit Number |
13010059 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-01-07 16:20:33 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY THE DESIGN WIND SPEED FOR THE STRUCTURE ON | | | THE PLANS WITH THE DESIGN CRITERIA ON SHEET A-2. FBCR | | | 301.2.1 | | | | | | 2) BASED ON FBCR 301.2.1.4.3 THE STRUCTURE IS LOCATED | | | IN EXPOSURE CATEGORY C NOT B. PLEASE REVISE. | | | | | | 3) PROVIDE A FLOOR PLAN OF THE EXISTING STRUCTURE PRIOR | | | TO THE REMODEL. CITY AMENDMENTS 107.2.1 | | | | | | 4) SPECIFY THE EXISTING AREA CALCULATIONS AND THE | | | PROPOSED AREA CALCULATIONS ON THE PLANS. CITY | | | AMENDMENTS 107.2.1.3 | | | | | | 5) NOTE: THE PLANS WILL BE REQUIRED TO BE REVIEWED BY | | | PALM BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES ARE | | | DUE. | | | | | | 6) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE ADDED | | | LIVING SPACE. FBC ENERGY CONSERVATION 401.2 | | | | | | 7) SPECIFY THE HORIZONTAL REINFORCEMENT FOR THE | | | CONCRETE BOND BEAM AT THE TOP OF THE STEM WALL. FBCR | | | 404.1.1.1.1 | | | | | | 8) SHOW COMPLIANCE WITH FBCR 806.1 FOR ATTIC | | | VENTILATION ON THE PLANS. | | | | | | 9) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE NEW | | | EXTERIOR DOORS, WINDOWS, STORM PANELS AS REQUIRED BY | | | DCA RULE 9N-3. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|