| Notes |
| Date |
Text |
| 2013-01-22 11:50:25 | *** PROVISO *** | | | 1) COMPLY WITH 2010 FBC/ENERGY 503.2.4.4 SHUTOFF DAMPER | | | CONTROLS. BOTH OUTDOOR AIR SUPPLY AND EXHAUST DUCTS | | | SHALL BE EQUIPPED WITH DAMPERS THAT WILL AUTOMATICALLY | | | SHUT WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE. | | | 2) REVISE MECH. PLAN M-1 TO SHOW CORRECT RETURN AIR | | | DUCT SIZES BEFORE ROUGH INSPECTION, PER 2010 CITY OF | | | WPB AMEND. 107.3.5.1.4 (6) AND 2010 FBC/M 601.4. | | | MECHANICAL PLAN REVIEW BY: | | | TOM GORDON (HY-BYRD INC.) (561) 805-6732 | | | | | 2013-01-16 14:31:49 | NEW SHEETS SUBMITTED. JG. |
|