| 2013-01-09 14:39:58 | FBC 2010 EXISTING BUILDING CODE |
| | FBC 2010 ACCESSIBILITY CODE |
| | FBC 2010 PLUMBING REVIEW #1 |
| | DENIED: |
| | |
| | 1. THE RESTROOM WILL BE REQUIRED TO BE A MINIMUM OF |
| | 7'-1" WIDE TO ACHIEVE THE REQUIRED 60" CLEAR SPACE FOR |
| | THE WATER CLOSET. (OTHER CONFIGURATIONS ARE ALSO |
| | POSSIBLE). |
| | FBC ACCESSIBILITY CODE 2010 604.3.1 SIZE. CLEARANCE |
| | AROUND A WATER CLOSET SHALL BE 60 INCHES (1525 MM) |
| | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND |
| | 56 INCHES (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM |
| | THE REAR WALL. |
| | FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL |
| | NOT BE PERMITTED IN THE 60" SPACE. |
| | PLEASE SEE FIGURE 604.8.1.6 ALSO. |
| | |
| | 2. IF A DRINKING FOUNTAIN IS PROVIDED IN THIS |
| | OCCUPANCY, IT WILL BE REQUIRED TO BE A HI/LO TYPE. |
| | |
| | FBC ACCESSIBILITY 2010 211.1 GENERAL. WHERE DRINKING |
| | FOUNTAINS ARE PROVIDED ON AN EXTERIOR SITE, ON A FLOOR, |
| | OR WITHIN A SECURED AREA THEY SHALL BE PROVIDED IN |
| | ACCORDANCE WITH 211. |
| | FBC ACCESSIBILITY 2010 211.2 MINIMUM NUMBER. NO FEWER |
| | THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE |
| | DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 |
| | AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. |
| | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| | FOUNTAINS. |
| | |
| | |