Plan Review Notes
Plan Review Notes For Permit 13010051
Permit Number 13010051
Review Stop M
Sequence Number 1
Notes
Date Text
2013-01-08 09:58:54*** PROVISO ***
 1) COMPLY WITH 2010 FBC/ENERGY 503.2.4.4 SHUTOFF DAMPER
 CONTROLS. BOTH OUTDOOR AIR SUPPLY AND EXHAUST DUCTS
 SHALL BE EQUIPPED WITH DAMPERS THAT WILL AUTOMATICALLY
 SHUT WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE.
 2) REVISE MECH. PLAN M-1 TO SHOW CORRECT RETURN AIR
 DUCT SIZES BEFORE ROUGH INSPECTION, PER 2010 CITY OF
 WPB AMEND. 107.3.5.1.4 (6) AND 2010 FBC/M 601.4.
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732
  