| 2013-02-07 14:16:56 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | COMMENTS FROM PREVIOUS LIST: |
| | |
| | 1. 1ST PORTION OF COMMENT OK (RE: CLEAR OPENING SIZE) |
| | |
| | STAIR LOCATIONS NOT SHOWN. IT IS NOT CLEAR WHETHER THE |
| | OPENINGS WITHIN 10' OF THE STAIRS ARE TO BE FIRE RATED. |
| | "STAIR" WAS WRITTEN ON THE PLAN WITH NO OTHER |
| | INFORMATION. PROVIDE A PLAN VIEW AND ELEVATIONS IF |
| | NECESSARY; ALL INFORMATION REQUIRED IN ORDER TO |
| | DEMONSTRATE CODE COMPLIANCE. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. THE PLAN SHOWS STAIRS BUT |
| | DOES NOT INCLUDE ANY DIMENSIONS TO WINDOWS TO BE |
| | REPLACED. THE PLAN PROVIDED DOES NOT APPEAR TO |
| | CORRELATE WITH BUILDING AERIALS. IN A CONVERSATION WITH |
| | THE CONTRACTOR, "STAIRS" AND "FIRE ESCAPES" WERE BOTH |
| | DISCUSSED. WHERE THESE ELEMENTS ARE LOCATED, HOW THEY |
| | AFFECT THE MEANS OF EGRESS, IS NOT CLEAR. FIRE DEPT WAS |
| | UNABLE TO CONFIRM INTEGRITY OF EXITS. ALSO FIRE DEPT |
| | PROVIDED INFORMATION THAT TWO SECTIONS OF THE BUILDINGS |
| | ARE SEPARATED (UNITS ON ONE WING DO NOT HAVE ACCESS TO |
| | EXITS IN THE OTHER WING), AND THIS IS NOT SHOWN ON THE |
| | PLAN. |
| | |
| | SEE FBC EXISTING BUILDING 101.5. COMPLIANCE METHOD IS |
| | NOT CLEAR. PRESCRIPTIVE COMPLIANCE (FBC EXISTING |
| | BUILDING 301.2.2), EITHER LIKE MATERIALS PROVIDED NO |
| | HAZARD TO LIFE, OR COMPLIANCE WITH REQUIREMENTS FOR NEW |
| | CONSTRUCTION. |
| | |
| | FBC EXISTING BUILDING 602.4, ALL NEW WORK TO COMPLY |
| | WITH REQUIREMENTS OF FLORIDA BUILDING CODE. |
| | |
| | PLEASE ALSO SEE FBC CHAPTER 13, PERFORMANCE COMPLIANCE |
| | METHODS. |
| | |
| | SEE FBC 1022.6 (EXIT ENCLOSURES) AND 1026.6, EXTERIOR |
| | STAIRS (WHICH REFERS TO 1022.6): |
| | |
| | OPENINGS WITHIN SUCH EXTERIOR WALLS SHALL BE PROTECTED |
| | BY OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING |
| | OF NOT LESS THAN 3/4 HOUR. |
| | |
| | **PLEASE NOTE THAT PROVIDING LIKE MATERIALS IS AN |
| | OPTION PROVIDED NO HAZARD TO LIFE. ** AN ACCURATE LIFE |
| | SAFETY PLAN AND ACCURATE ELEVATIONS, WITH DIMENSIONS |
| | WOULD BE HELPFUL IN ORDER TO DETERMINE HAZARD TO LIFE |
| | AND WHETHER RATED OPENINGS WOULD BE REQUIRED. |
| | OTHERWISE, PROVIDE A PLAN WHICH SHOWS ENOUGH |
| | INFORMATION TO SHOW COMPLIANCE WITH FBC 1022.6. |
| | |
| | 2. OK. |
| | |
| | |
| | |
| | |
| | |
| | |