| 2013-01-08 10:59:48 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SPECIFY THE DESIGN CRITERIA, WINDSPEED AND EXPOSURE |
| | CATEGORY ON THE PLANS. FBC R301.2.1 AND CITY AMENDMENTS |
| | 107.3.5.3 |
| | |
| | 2) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE |
| | NEW EXTERIOR DOORS ON THE PLANS. FBC R301.2.1 |
| | |
| | 3) SPECIFY THE SIZES OF THE NEW DOORS ON THE PLANS. FBC |
| | R301.2.1 AND CITY AMENDMENTS 107.2.1 |
| | |
| | 4) PROVIDE STRUCTURAL DETAILS FOR THE NEW DOOR OPENINGS |
| | ON THE PLANS. IF WOOD FRAME, INCLUDE HEADER SIZE, |
| | FRAMING & STRAPPING INFORMATION. IF MASONRY |
| | CONSTRUCTION PROVIDE LINTEL INFORMATION AND STEEL |
| | REINFORCING DETAILS. CITY AMENDMENTS 107.2.1 AND |
| | 107.2.1.3 |
| | |
| | 5) PROVIDE STRUCTURAL DETAILS FOR THE NEW STAIRS. SHOW |
| | COMPLIANCE WITH FBCR 311.7.4 FOR TREADS & RISERS, FBCR |
| | 311.7.7 FOR HANDRAILS AND FBCR 312 FOR GUARDS. |
| | |
| | 6) PROVIDE STRUCTURAL DETAILS FOR THE PROPOSED HEADER |
| | AT THE WALL BESIDE THE STAIRS AND SHOW CONTINUOUS LOAD |
| | PATH TO FOUNDATION. FBCR 301.1 AND CITY AMENDMENTS |
| | 107.2.1 |
| | |
| | 7) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR REQUIRED SMOKE |
| | ALARMS. |
| | |
| | 8) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | NEW EXTERIOR DOORS ARE FOR INSWING DOORS, HOWEVER, THE |
| | DOORS SHOWN ON THE PLANS ARE OUTSWING. PLEASE CORRECT. |
| | DCA RULE 9N-3. |
| | |
| | 9) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PER |
| | CITY AMENDMENTS 107.3.5.3. |
| | |
| | 10) THE ARCHITECT'S ORIGINAL SIGNATURE IS REQUIRED ON |
| | THE PLANS. SIGNATURE STAMPS OR PHOTO COPIED SIGNATURES |
| | ARE NOT ACCEPTABLE . FS 481 AND FAC 61G1-16.003 |
| | |