| 2013-01-07 11:23:15 | *** CORRECTIONS NEEDED TO MECHANICAL PLAN REVISION *** |
| | |
| | 1) NEED THE DESIGNER'S INFORMATION ON THE PLAN, COMPANY |
| | NAME, LICENSE NUMBER, INDIVIDUAL'S NAME, ETC. THAT |
| | APPLY. SEE 2004 FBC 106.1. |
| | |
| | 2) PLANS SUBMITTED ARE DIFFICULT TO READ. SEE 2004 FBC |
| | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE |
| | PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5). |
| | |
| | 3) THE FOLLOWING CORRECTIONS ARE NEEDED TO COMPLY WITH |
| | 2004 FBC 106.3.5. |
| | (A) CAN NOT DETERMINE IF THE AIR HANDLER UNITS ARE IN |
| | THE ATTIC OR CLOSET. |
| | (B) CAN NOT TELL WHAT DUCT SIZES GO TO WHAT DUCTS. |
| | (C) CAN NOT DO A PROPER REVIEW DUE TO THE QUALITY OF |
| | THE PLANS. |
| | |
| | 4) NEED TO SHOW THE EQUIPMENT LISTING ON THE PLANS WITH |
| | THE PROPER INFORMATION, PER 2004 CITY OF WPB AMEND. |
| | 106.3.5.4 (10). |
| | |
| | 5) SHOW THE LOCATION & SIZE OF THE BATHROOM EXHAUST |
| | FANS AND CLOTHES DRYER VENT ON PLANS, AND THAT THEY |
| | COMPLY WITH 2004 FBC/R M1502 AND TABLE M1507.3. |
| | |
| | MECHANICAL PLAN REVIEW BY: |