| Plan Review Notes For Permit 12120776 |
| Permit Number |
12120776 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-01-28 16:30:59 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | FROM PREVIOUS LIST: | | | | | | FBC R 301, RESISTANCE TO WIND LOADS: | | | | | | 1. OK | | | | | | 2. INDICATE WHICH APPROVED ASSEMBLY IS PROPOSED. | | | | | | 2ND REVIEW, THE ASSEMBLY ON SHEET 21 HIGHLIGHTED. IF | | | YOU USE THIS ASSEMBLY, ENHANCED FASTENING CALCULATIONS | | | REQUIRED. PLEASE NOTE THAT THE ASSEMBLY ON SHEET 23 | | | COMPLIES WITH DESIGN PRESSURE FOR ZONE 3 AND ENHANCED | | | FASTENING SPECIFIED BY AN ARCHITECT OR ENGINEER WOULD | | | NOT THEN BE REQUIRED. | | | | | | 3. ENHANCED FASTENING NAILING IS TO STATE NUMBER OF | | | FIELD ROWS. | | | | | | 2ND REVIEW, ENHANCED FASTENING CALCULATIONS NOT | | | SUBMITTED. | | | | | | 4. OK | | | | | | NEW COMMENT: | | | | | | PER BUILDING OFFICIAL, THIS IS NOT A SUB PERMIT, THIS | | | SHOULD BE A REVISION TO THE MASTER AND THEN A SUB | | | PERMIT CAN BE ISSUED AFTER REVISION HAS BEEN REVIEWED | | | AND PASSED. THIS COMMENT DOES NOT NEED TO BE ADDRESSED | | | BUT ADJUSTMENTS TO FEES SHALL BE MADE PRIOR TO | | | ISSUANCE. | | | |
|