| Plan Review Notes For Permit 12120755 |
| Permit Number |
12120755 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-01-02 10:04:23 | 1212075 | | | 771 W. EXECUTIVE CENTER DRIVE | | | COMMERCIAL RENOVATION | | | TEMPORARY FIRE STATION | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | | GENERAL PURPOSE OUTLETS SERVING SLEEPING AREAS. NEC | | | 210.18 | | | GFCI PROTECTION IS REQUIRED FOR ALL OUTDOOR | | | RECEPTACLES. NEC 210.8 (B) | | | GFCI PROTECTION IS REQUIRED FOR THE CORD REEL. NEC | | | 210.8 (B) | | | GFCI PROTECTION IS REQUIRED FOR ALL BATHROOM | | | RECEPTACLES. NEC 210.8 (B) | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|