| 2013-01-11 16:36:31 | 12120739 | | | 5726 PREMIER PARK DR | | | STORAGE WITH SERVER ROOM | | | | | | THE FOLLOWING ITEMS HAVE BEEN NOTED ON THE PLANS. | | | | | | PROVIDE SAFETY LABELING FOR FLASH PROTECTION AND FOR | | | THE MAIN DISCONNECTING MEANS. | | | NEC 110.22, 110.16, 110.22 | | | | | | VENDING MACHINES SHALL BE PROTECTED WITH GFCI? S. NEC | | | 422.51 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|