| 2013-01-16 14:30:29 | BUILDING PLAN REVIEW |
| | PERMIT: 12120739 |
| | ADD: 5726 PREMIER PARK |
| | CONT: DUKE INDIANA CONSTRUCTION |
| | TEL: (954)453-5660 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | JAN. 16/2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1.1 THE THREE VAULT WALLS ARE INDICATED AS A |
| | 2HR WALL WITH SECTION A4/ A3.3 BUT THE TENAT SEPERATION |
| | WALL DOES NOT IDENTY THE EXISTING WALL TYPE BEING A TWO |
| | HOUR WALL? ADDITIONAL INFORMATION REQUIRED.107.2.1.3. |
| | |
| | 2) SHEET A1.2 THE DEAD END CORRIDOR IS INDICATED AS |
| | 76'-11" LONG, PLEASE REVIEW 2010 FBC-B 1018.4 EXCEPTION |
| | # 2 LIMITS A DEAD END CORRIDOR TO 50' IN A STORAGE |
| | OCCUPANCY. |
| | |
| | 3) SHEET A1.2 BUSINESS OCCUPANCY ROOM 117 SCANNING |
| | STATIONS, FROM THE FURTHEST POINT IN THE ROOM IS OVER |
| | 100' TO THE EXTERIOR EXIT DOOR. THE PLANS CURRENTLY |
| | SHOW A SECOND MEANS OF EGRESS THROUGH THE STORAGE |
| | OCCUPANCY. 2010 FBC-B WILL ALLOW YOU TO GO THROUGH |
| | INTERVENING ROOMS AND OR SPACES IF THEY ARE THE SAME OR |
| | LESSER HAZARD OCCUPANCY GROUP, STORAGE OCCUPANCIES ARE |
| | A HIGHER OCCUPANCY HAZARD CLASSIFICATION PLEASE SEE |
| | 2010 FBC-B 1014.2 .1 EXCEPTION. |
| | |
| | 4) SHEET A3.4 DETAIL J11 PLEASE PROVIDE MANUFACTURERS |
| | SPEC FOR DOCK LEVELERS. NOTE INDICATES FINAL ROUGH-IN |
| | FOR PIT TO BE DETERMINED AND COORDINATED WITH DOCK |
| | LEVELER |
| | MANUFACTURER RECOMMENDATIONS. 107.2.1.3. ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 5) SHEET M7.1 HVAC ROOF TOP CURB DETAIL DOES HAVE A |
| | SPECIAL NOTE THE CURB SHALL BE ATTACHED BY A LICENSED |
| | STRUCTURAL ENGINEER. |
| | |
| | 6) SHEET M7.1 A/C EQUIPMENT MOUNTING DETAIL, FOR |
| | PRE-ENGINEERED A/C STANDS PLEASE SEE RULE 9N-3 (31) (G) |
| | REQUIRES EITHER FLORIDA STATE APPROVAL OR A MIAMI-DADE |
| | NOA. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |