| Notes |
| Date |
Text |
| 2014-06-30 11:52:03 | 2010 FBC | | | | | | TRUSS DRAWINGS ARE DENIED | | | | | | 1) THE DESIGNER OF RECORD FOR THE STRUCTURE HAS | | | INDICATED THAT THE TRUSS LAYOUT AND DRAWINGS FOR THE | | | MODEL E HIP OPTION DO NOT MATCH THE STRUCTURAL PLANS. | | | THE FRAMING AT THE FRONT PORCH IS DIFFERENT THAN THE | | | PLANS. | | | | | | 2) THE TRUSS DRAWINGS FOR THE MODEL E GABLE OPTION DO | | | NOT HAVE THE DESIGNER OF RECORDS SHOP REVIEW STAMP ON | | | THEM. THEY WILL NEED TO BE REVIEWED BY THE D.O.R. IT | | | APPEARS THAT THE TRUSS LAYOUT AND DRAWINGS FOR THIS | | | OPTION DOES NOT MATCH THE STRUCTURAL PLANS. THE TRUSS | | | DRAWINGS HAVE A TWO PLY GIRDER (B5) NEAR THE FRONT | | | PORCH AND THE STRUCTURAL DRAWING SHOW THE TRUSSES | | | BEARING ON THE EXTERIOR WALL. | | | | | | 3) THE TRUSS LAYOUT PLANS ARE NOT SIGNED AND SEALED BY | | | THE TRUSS ENGINEER. FS 471 & FAC 61G-31.003 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|