| 2013-09-18 14:58:38 | 2008 NEC | | | | | | DENIED BY ELECTRIC | | | | | | 1) THE MECHANICAL EQUIPMENT SCHEDULE SPECIFIES THE | | | MAXIMUM OVER CURRENT PROTECTION FOR THE CONDENSING UNIT | | | TO BE 35 AMPS. THE ELECTRICAL PANEL SCHEDULE SHOWS A 40 | | | AMP BREAKER. PLEASE CORRECT. | | | | | | 2) THE MECHANICAL EQUIPMENT SCHEDULE SPECIFIES THE | | | MAXIMUM OVER CURRENT PROTECTION FOR THE AIR AHANDLER | | | UNIT TO BE 30 AMPS. THE ELECTRICAL PANEL SCHEDULE SHOWS | | | A 45 AMP BREAKER. PLEASE CORRECT. | | | | | | 3) PROVIDE A 2ND GROUND ROD TO MEET REQUIRED OHM | | | RESISTANCE. NEC 250.56 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|