| Plan Review Notes For Permit 12120698 |
| Permit Number |
12120698 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-02-12 15:20:46 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE WINDLOAD PRESSURES FOR THE OVERHEAD GARAGE DOOR | | | SPECIFIED ON SHEET S-1 OF THE PLANS IS HIGHER THAN | | | REQUIRED. THE PRODUCT APPROVAL THAT IS SUBMITTED IS | | | REQUIRED TO MEET OR EXCEED THE PRESSURES SPECIFIED ON | | | THE PLANS. DCA RULE 9N-3. | | | | | | 2) SUBMIT TWO COPIES OF A SURFACE DRAINAGE PLAN SHOWING | | | COMPLIANCE WITH FBCR 401.3. THESE CAN BE SUBMITTED WITH | | | EACH PERMIT APPLIED FOR UNDER THE MASTER. | | | | | | 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR EXTERIOR | | | WINDOWS, DOORS, OVERHEAD GARAGE DOORS, ROOFING | | | MATERIAL, BLOCK LINTELS, TRUSS ANCHORS, MULLIONS, | | | HARDI-PLANK SIDING, ETC. AS REQUIRED BY DCA RULE 9N-3. | | | | | | 4) THE PRODUCT APPROVALS ARE REQUIRED TO REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PER CITY | | | AMENDMENTS 107.3.4.1. | | | | | | 5) SUBMIT TWO SETS OF SIGNED AND SEALED TRUSS DRAWINGS | | | AND LAYOUTS THAT HAVE BEEN REVIEWED AND APPROVED BY THE | | | DESIGNER OF RECORD. FBCR 802.1.6.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|