| Plan Review Notes For Permit 12120697 |
| Permit Number |
12120697 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-09-17 18:43:17 | 2008 NEC | | | | | | DENIED BY ELECTRIC | | | | | | 1) THE MECHANICAL EQUIPMENT SCHEDULE SPECIFIES THE | | | MAXIMUM OVER CURRENT PROTECTION FOR THE CONDENSING UNIT | | | TO BE 30 AMPS. THE ELECTRICAL PANEL SCHEDULE SHOWS A 40 | | | AMP BREAKER. PLEASE CORRECT. | | | | | | 2) PROVIDE A 2ND GROUND ROD TO MEET REQUIRED OHM | | | RESISTANCE. NEC 250.56 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|