| Date |
Text |
| 2013-01-03 13:16:50 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND |
| | SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE |
| | SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1. |
| | |
| | 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS AS REQUIRED |
| | BY FBC ENERGY CONSERVATION SECTION 405.4. |
| | |
| | 3) UPDATE THE WIND SPEED INFORMATION ON SHEET S-2 TO |
| | 170 MPH VULT / 132 VASD. FBCR301.2.1 |
| | |
| | 4) UPDATE THE CODE AND STANDARDS REFERENCED ON SHEET |
| | S-2 TO FBC 2010, ACI 318 - 2008, ACI 530 - 2008 AND ACI |
| | 315 - 2008. FBCR CHAPTER 43 |
| | |
| | 5) EXPOSURE CATEGORY C IS SPECIFIED ON THE PLANS. NOTE: |
| | IF THERE ARE ANY STRUCTURES THAT WILL BE CONSTRUCTED |
| | UNDER THIS MASTER WITHIN 600 FT OF THE INTER-COASTAL |
| | WATERWAY OR OTHER BODY OF WATER WITH A ONE MILE FETCH |
| | THEN THEY ARE CONSIDERED EXPOSURE D. FBCR 301.2.1.4.2 |
| | |
| | 6) SUBMIT TWO COPIES OF A SURFACE DRAINAGE PLAN. |
| | FBCR401.3 |
| | |
| | 7) UPDATE CODE AND STANDARDS ON THE COVER SHEET (IE |
| | 2010 FBC, 2010 FIRE PREVENTION CODE,2008 NEC). NOTE: |
| | THE FAIRHOUSING GUIDELINES DO NOT APPLY TO ONE AND TWO |
| | FAMILY DWELLINGS. |
| | |
| | 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR EXTERIOR |
| | WINDOWS, DOORS, ROOFING MATERIAL, BLOCK LINTELS, TRUSS |
| | ANCHORS, ETC. AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 9) PRODUCT APPROVALS ARE REQUIRED TO REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PER CITY |
| | AMENDMENTS 107.3.4.1. |
| | |
| | NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS |
| | RED-LINED TO SHOW WHERE CORRECTIONS WERE NEEDED. |
| | |