| 2012-12-27 15:11:52 | *** MECHANICAL CORRECTIONS NEEDED *** |
| | |
| | 1) SUBMIT COMPLETE COOLING LOAD CALCULATIONS, NOT A ONE |
| | PAGE SUMMERY SHEET. SEE 2010 FBC/ENERGY 101.4.7.1.2 |
| | REPLACEMENT EQUIPMENT SIZING (MANDATORY). AN A/C |
| | CONTRACTOR OR LICENSED FLORIDA PE SHALL SUBMIT A |
| | NATIONALLY RECOGNIZED METHOD BASED SIZING CALCULATION |
| | TO THE CODE OFFICIAL AT THE TIME OF PERMIT APPLICATION |
| | FOR TOTAL REPLACEMENT OF THE CONDENSING AND EVAPORATOR |
| | COMPONENTS OF HVAC SYSTEMS IN ACCORDANCE WITH FLORIDA |
| | LAW AND THE PROVISIONS OF SECTION 403.6.1 OR SECTION |
| | 503.2.1, AS APPLICABLE. |
| | |
| | 2) SUBMIT AIR DUCT CALCULATIONS. SEE 2010 FBC/R M1601.1 |
| | DUCT DESIGN. DUCT SYSTEMS SERVING HEATING, COOLING AND |
| | VENTILATION EQUIPMENT SHALL BE FABRICATED IN ACCORDANCE |
| | WITH THE PROVISIONS OF THIS SECTION AND ACCA MANUAL D |
| | OR OTHER APPROVED METHODS BASED ON THE FOLLOWING: (1) |
| | CALCULATION OF THE SUPPLY AIR FOR EACH ROOM SHALL BE |
| | BASED ON THE GREATER OF THE HEATING LOAD OR SENSIBLE |
| | COOLING LOAD FOR THAT ROOM. (2) DUCT SIZE SHALL BE |
| | DETERMINED BY THE SUPPLY AIR REQUIREMENTS OF EACH ROOM, |
| | THE AVAILABLE STATIC PRESSURE AND THE TOTAL EQUIVALENT |
| | LENGTH OF THE VARIOUS DUCT RUNS. (3) FRICTION LOSS DATA |
| | SHALL CORRESPOND TO THE TYPE OF MATERIAL USED IN DUCT |
| | CONSTRUCTION. |
| | |
| | 3) PLAN DOES NOT SHOW HOW THE AIR IS TO RETURN TO THE |
| | AIR HANDLER UNIT. SEE 2010 FBC/R M 1602.4. |
| | |
| | 4) MECHANICAL PLANS HAVE TO MUCH FLOOR PLAN DETAIL ON |
| | THEM AND ARE DIFFICULT TO READ THE MECHANICAL |
| | INFORMATION. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY. PER 2010 FBC 107.2.1. |
| | |
| | 5) THE MECHANICAL PLANS SUBMITTED HAVE AN ARCHITECT'S |
| | INFORMATION IN THE TITLE BLOCK AND NEED TO BE SIGNED |
| | AND SEALED BY THAT ARCHITECT. SEE FAC 61G1-16.004. OR |
| | REMOVE THE ARCHITECT'S INFORMATION FROM THE TITLE |
| | BLOCK. |
| | |
| | 6) ADD A/C SYSTEMS INFORMATION ON THE PLANS. MAKE, |
| | MODEL NUMBERS, SIZE, SEER, BTU'S. SENSIBLE & TOTAL, |
| | HEATER SIZE, ETC. PER 2010 CITY OF WPB AMEND. 107.3.5.3 |
| | (10). |
| | |
| | 7) SHOW ON PLANS WERE THE CONDENSATE DRAIN WILL |
| | DISCHARGE AT. SEE 2010 FBC/R M1411.3. |
| | |
| | 8) SHOW THE CFM'S OF AIR AT EACH SUPPLY GRILL. SEE 2010 |
| | FBC/R M1601.1. |
| | |
| | MECHANICAL PLAN REVIEW BY: |
| | TOM GORDON (HY-BYRD INC.) (561) 805-6732 |