Plan Review Notes
Plan Review Notes For Permit 12120696
Permit Number 12120696
Review Stop M
Sequence Number 1
Notes
Date Text
2012-12-27 15:11:52*** MECHANICAL CORRECTIONS NEEDED ***
  
 1) SUBMIT COMPLETE COOLING LOAD CALCULATIONS, NOT A ONE
 PAGE SUMMERY SHEET. SEE 2010 FBC/ENERGY 101.4.7.1.2
 REPLACEMENT EQUIPMENT SIZING (MANDATORY). AN A/C
 CONTRACTOR OR LICENSED FLORIDA PE SHALL SUBMIT A
 NATIONALLY RECOGNIZED METHOD BASED SIZING CALCULATION
 TO THE CODE OFFICIAL AT THE TIME OF PERMIT APPLICATION
 FOR TOTAL REPLACEMENT OF THE CONDENSING AND EVAPORATOR
 COMPONENTS OF HVAC SYSTEMS IN ACCORDANCE WITH FLORIDA
 LAW AND THE PROVISIONS OF SECTION 403.6.1 OR SECTION
 503.2.1, AS APPLICABLE.
  
 2) SUBMIT AIR DUCT CALCULATIONS. SEE 2010 FBC/R M1601.1
 DUCT DESIGN. DUCT SYSTEMS SERVING HEATING, COOLING AND
 VENTILATION EQUIPMENT SHALL BE FABRICATED IN ACCORDANCE
 WITH THE PROVISIONS OF THIS SECTION AND ACCA MANUAL D
 OR OTHER APPROVED METHODS BASED ON THE FOLLOWING: (1)
 CALCULATION OF THE SUPPLY AIR FOR EACH ROOM SHALL BE
 BASED ON THE GREATER OF THE HEATING LOAD OR SENSIBLE
 COOLING LOAD FOR THAT ROOM. (2) DUCT SIZE SHALL BE
 DETERMINED BY THE SUPPLY AIR REQUIREMENTS OF EACH ROOM,
 THE AVAILABLE STATIC PRESSURE AND THE TOTAL EQUIVALENT
 LENGTH OF THE VARIOUS DUCT RUNS. (3) FRICTION LOSS DATA
 SHALL CORRESPOND TO THE TYPE OF MATERIAL USED IN DUCT
 CONSTRUCTION.
  
 3) PLAN DOES NOT SHOW HOW THE AIR IS TO RETURN TO THE
 AIR HANDLER UNIT. SEE 2010 FBC/R M 1602.4.
  
 4) MECHANICAL PLANS HAVE TO MUCH FLOOR PLAN DETAIL ON
 THEM AND ARE DIFFICULT TO READ THE MECHANICAL
 INFORMATION. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2010 FBC 107.2.1.
  
 5) THE MECHANICAL PLANS SUBMITTED HAVE AN ARCHITECT'S
 INFORMATION IN THE TITLE BLOCK AND NEED TO BE SIGNED
 AND SEALED BY THAT ARCHITECT. SEE FAC 61G1-16.004. OR
 REMOVE THE ARCHITECT'S INFORMATION FROM THE TITLE
 BLOCK.
  
 6) ADD A/C SYSTEMS INFORMATION ON THE PLANS. MAKE,
 MODEL NUMBERS, SIZE, SEER, BTU'S. SENSIBLE & TOTAL,
 HEATER SIZE, ETC. PER 2010 CITY OF WPB AMEND. 107.3.5.3
 (10).
  
 7) SHOW ON PLANS WERE THE CONDENSATE DRAIN WILL
 DISCHARGE AT. SEE 2010 FBC/R M1411.3.
  
 8) SHOW THE CFM'S OF AIR AT EACH SUPPLY GRILL. SEE 2010
 FBC/R M1601.1.
  