| Notes |
| Date |
Text |
| 2013-01-04 15:43:39 | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. TABLE 402.4(2) AT 90' | | | LONGEST LENGTH METHOD REQUIRES 1 1/4" PIPE FROM THE | | | METER UP TO THE TEE FOR THE GAS RANGE. (THE SPECIFIC | | | GRAVITY FOR THIS TABLE IS .60) | | | | | | **NOTE** | | | WAS THE APPLIANCE LABELED GAS WASHER MEANT TO BE GAS | | | DRYER? | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|