Plan Review Notes
Plan Review Notes For Permit 12120635
Permit Number 12120635
Review Stop B
Sequence Number 2
Notes
Date Text
2013-01-16 16:35:25BUILDING PLAN REVIEW
 PERMIT: 12120635
 ADD: 2015 OKEECHOBEE BLVD.
 CONT: THE SINCLAIR GROUP
 TEL: (954)798-1421
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 BUILDING PROVISO:
  
 THE FOLLOWING LIST OF CODE ISSUES WILL NEED TO BE
 SATISFIED BY THE ROOF FRAMING AND DOOR / WINDOW BUCK
 INSPECTION, NO INTERIOR FRAMING AND OR TRADE WORK (MEP)
 ALLOWED BEFORE THESE CODE ISSUES ARE SATISFIED.
  
 1) COMPLIED 01/16/2013. MISSING SOILS REPORT. 2010
 FBC-B / 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1803.3.1 & 1803.6 REPORTING.
  
 2) SEMI-COMPLIED 01/16/ 2013. MISSING ENERGY
 CALCULATIONS. 2010 FBC-B 103.3 ENERGY CODE COMPLIANCE.
 ENERGY CALCULATIONS.
 EXAMINATION OF DOCUMENTS. THE CODE OFFICIAL SHALL
 EXAMINE OR CAUSE TO BE EXAMINED THE ACCOMPANYING
 CONSTRUCTION DOCUMENTS AND SHALL ASCERTAIN WHEATHER THE
 CONSTRUCTION INDICATED AND DESCRIBED IS IN ACCORDANCE
 WITH THE REQUIREMENTS OF THIS CODE AND OTHER PERTINENT
 LAWS OR ORDINANCES.
  
 2A) SHOW COMPLIANCE WITH 2010 ENERGY CODE 402.1.2.3
 MAXIMUM PER CENT WINDOW AREA.
  
 2B) PROVIDE COMPLIANCE WITH 2010 ENERGY CODE TABLE
 402.1.1 GLAZED FENESTRATION SHGC
  
 3) SHEET A-506 DETAIL # 2,:
  
 3A) INDICATES THE USE OF R-40 EXPANDABLE FOAM
 INSULATION, PLEASE PROVIDE WHAT THE THICKNESS OF THE
 EXPANDED FOAM WILL BE FOR THE ROOF INSULATION AND THE
 WALL INSULATION. PLEASE PROVIDE A PRODUCT APPROVAL FOR
 THIS PRODUCT.
  
 3B) PLANS FAIL TO IDENTIFY THE USE OF AN IGNITION
 BARRIER, PER 2010 FBC-B 2603.4.1.6 ALSO SEE BOAF
 INTERPRETATION 5416.
  
 3C) PLANS ALSO FAIL TO PROVIDE COMPLIANCE WITH 2010
 FBC-B 2603.4 THERMAL BARRIER. EXCEPT AS PROVIDED FOR IN
 SECTIONS 2603.4.1 AND 2603.9, FOAM PLASTIC SHALL BE
 SEPARATED FROM THE INTERIOR OF A BUILDING BY AN
 APPROVED THERMAL BARRIER OF 1/2-INCH (12.7 MM) GYPSUM
 WALLBOARD OR EQUIVALENT THERMAL BARRIER MATERIAL THAT
 WILL LIMIT THE AVERAGE TEMPERATURE RISE OF THE
 UNEXPOSED SURFACE TO NOT MORE THAN 250?F (120?C) AFTER
 15 MINUTES OF FIRE EXPOSURE, COMPLYING WITH THE
 STANDARD TIME-TEMPERATURE CURVE OF ASTM E 119 OR UL
 263. THE THERMAL BARRIER SHALL BE INSTALLED IN SUCH A
 MANNER THAT IT WILL REMAIN IN PLACE FOR 15 MINUTES
 BASED ON FM 4880, UL 1040, NFPA 286 OR UL 1715.
 COMBUSTIBLE CONCEALED SPACES SHALL COMPLY WITH SECTION
 717.
  
 THE PLANS INDICATE THE USE OF A BLACK FIBERGLASS
 INSULATION, PLEASE PROVIDE EQUIVALENCY.
  
 4) G-002 DOES PROVIDE A LIST OF PROPOSED PRODUCT
 APPROVALS BUT NO REPORTS WERE SUBMITTED. WITHOUT THE
 ACTUAL REPORTS REVIEW FOR CODE COMPLIANCE CAN NOT BE
 ACHIEVED.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) REPORTS FOR GLAZED OPENINGS, PLEASE CIRCLE THE TYPE
 OF GLAZING TO BE INSTALLED, CIRCLE MULLION TYPES AND IF
 REINFORCING IS REQUIRED, LENGTH & WIDTH OF OPENINGS,
 AND ASSOCATED PRESSURES.
  
 6) ROOFING REPORTS, WITHIN MANY ROOFING REPORTS, THERE
 ARE NUMEROUS SUB-SYSTEMS, PLEASE CIRCLE THE TYPE OF
 SUB-SYSTEM TO BE INSTALLED, REVIEW THE ASSOCATED
 PRESSURES, IF THE PRODUCT APPROVAL ALLOWS FOR ENHANCED
 FASTENING IN ZONES 2 & 3 OR NOT. SEE IF THE PRODUCT
 APPROVAL REQUIRES A DESIGN PROFESSIONAL FOR RAS 117
 CALCULATIONS.
  
 7)COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  