Plan Review Notes
Plan Review Notes For Permit 12120635
Permit Number 12120635
Review Stop E
Sequence Number 1
Notes
Date Text
2013-01-03 12:58:51125120635
 2015 OKEECHOBEE BLVD.
 PDQ RESTAURANT
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE THE REQUIRED FAULT CURRENT CAPABILITY OF THE
 SERVICE EQUIPMENT AND PANEL BOARDS. NEC 110.9
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE
 WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC
 ENERGY CONSERVATION 505.3
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION. NEC 110.22,
 110.16
  
 INDICATE THE REQUIRED SAFE CLEARANCES TO THE CEILING
 FANS. NEC 110.3
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA, FIRE ALARM, SECURITY, SIGNAGE, AND SITE LIGHTING.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  