Plan Review Notes
Plan Review Notes For Permit 12120635
Permit Number 12120635
Review Stop B
Sequence Number 1
Notes
Date Text
2013-01-02 09:24:41BUILDING PLAN REVIEW
 PERMIT: 12120635
 ADD: 2015 OKEECHOBEE BLVD.
 CONT: THE SINCLAIR GROUP
 TEL: (954)798-1421
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 JAN. 02/ 2013
 ACTION: DENIED
  
 1) MISSING SOILS REPORT. 2010 FBC-B / 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1803.3.1 & 1803.6
 REPORTING.
  
 2) MISSING ENERGY CALCULATIONS. 2010 FBC-B 103.3 ENERGY
 CODE COMPLIANCE. ENERGY CALCULATIONS.
 EXAMINATION OF DOCUMENTS. THE CODE OFFICIAL SHALL
 EXAMINE OR CAUSE TO BE EXAMINED THE ACCOMPANYING
 CONSTRUCTION DOCUMENTS AND SHALL ASCERTAIN WHEATHER THE
 CONSTRUCTION INDICATED AND DESCRIBED IS IN ACCORDANCE
 WITH THE REQUIREMENTS OF THIS CODE AND OTHER PERTINENT
 LAWS OR ORDINANCES.
  
 2A) SHOW COMPLIANCE WITH 2010 ENERGY CODE 402.1.2.3
 MAXIMUM PER CENT WINDOW AREA.
  
 2B) PROVIDE COMPLIANCE WITH 2010 ENERGY CODE TABLE
 402.1.1 GLAZED FENESTRATION SHGC
  
 3) SHEET A-506 DETAIL # 2,:
  
 3A) INDICATES THE USE OF R-40 EXPANDABLE FOAM
 INSULATION, PLEASE PROVIDE WHAT THE THICKNESS OF THE
 EXPANDED FOAM WILL BE FOR THE ROOF INSULATION AND THE
 WALL INSULATION. PLEASE PROVIDE A PRODUCT APPROVAL FOR
 THIS PRODUCT.
  
 3B) PLANS FAIL TO IDENTIFY THE USE OF AN IGNITION
 BARRIER, PER 2010 FBC-B 2603.4.1.6 ALSO SEE BOAF
 INTERPRETATION 5416.
  
 3C) PLANS ALSO FAIL TO PROVIDE COMPLIANCE WITH 2010
 FBC-B 2603.4 THERMAL BARRIER. EXCEPT AS PROVIDED FOR IN
 SECTIONS 2603.4.1 AND 2603.9, FOAM PLASTIC SHALL BE
 SEPARATED FROM THE INTERIOR OF A BUILDING BY AN
 APPROVED THERMAL BARRIER OF 1/2-INCH (12.7 MM) GYPSUM
 WALLBOARD OR EQUIVALENT THERMAL BARRIER MATERIAL THAT
 WILL LIMIT THE AVERAGE TEMPERATURE RISE OF THE
 UNEXPOSED SURFACE TO NOT MORE THAN 250?F (120?C) AFTER
 15 MINUTES OF FIRE EXPOSURE, COMPLYING WITH THE
 STANDARD TIME-TEMPERATURE CURVE OF ASTM E 119 OR UL
 263. THE THERMAL BARRIER SHALL BE INSTALLED IN SUCH A
 MANNER THAT IT WILL REMAIN IN PLACE FOR 15 MINUTES
 BASED ON FM 4880, UL 1040, NFPA 286 OR UL 1715.
 COMBUSTIBLE CONCEALED SPACES SHALL COMPLY WITH SECTION
 717.
  
 THE PLANS INDICATE THE USE OF A BLACK FIBERGLASS
 INSULATION, PLEASE PROVIDE EQUIVALENCY.
  
 4) G-002 DOES PROVIDE A LIST OF PROPOSED PRODUCT
 APPROVALS BUT NO REPORTS WERE SUBMITTED. WITHOUT THE
 ACTUAL REPORTS REVIEW FOR CODE COMPLIANCE CAN NOT BE
 ACHIEVED.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) REPORTS FOR GLAZED OPENINGS, PLEASE CIRCLE THE TYPE
 OF GLAZING TO BE INSTALLED, CIRCLE MULLION TYPES AND IF
 REINFORCING IS REQUIRED, LENGTH & WIDTH OF OPENINGS,
 AND ASSOCATED PRESSURES.
  
 6) ROOFING REPORTS, WITHIN MANY ROOFING REPORTS, THERE
 ARE NUMEROUS SUB-SYSTEMS, PLEASE CIRCLE THE TYPE OF
 SUB-SYSTEM TO BE INSTALLED, REVIEW THE ASSOCATED
 PRESSURES, IF THE PRODUCT APPROVAL ALLOWS FOR ENHANCED
 FASTENING IN ZONES 2 & 3 OR NOT. SEE IF THE PRODUCT
 APPROVAL REQUIRES A DESIGN PROFESSIONAL FOR RAS 117
 CALCULATIONS.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  