| Plan Review Notes For Permit 12120569 |
| Permit Number |
12120569 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-20 10:49:46 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. SQUARE FOOT AREA ON APPLICATION (800SF) DOES NOT | | | MATCH PAPA RECORDS. PLEASE CLARIFY ROOF AREA PROPOSED | | | FOR REROOF. | | | | | | 2. THE ASSSEMBLY ON PAGE 14 IS CIRCLED, BUT DOES NOT | | | MATCH THE PROPOSED ENHANCED FASTENING LETTER WHICH | | | REFERS TO DESIGN PRESSURE OF -52.5 AND RING SHANK | | | NAILS. FASTENING FOR ASSEMBLIES ON SELECTED PAGE USES | | | SIMPLEX MEGA CAP NAILS, -45 AND -60PSF. | | | |
|