2012-12-18 15:36:18*** CORRETCIONS NEEDED TO MECHANICAL PLANS ***
  
 1) EXPLAIN THE USE OF THE BUILDING FOR PROPER PLAN
 REVIEW.
  
 2) MECHANICAL PLAN SUBMITTED DOES NOT SHOW IF THE AHU'S
 ARE HANGING OR ON STANDS WHAT SIZE THE DUCTS ARE,
 LOCATION OF RETURN GRILLS, SUPPLY GRILL SIZES, WHERE
 THE CONDENSATE LINES DRAIN TO, IF THE CONDENSER UNITS
 ARE ON THE ROOF OR SIDE OF BUILDING' HOW THE FRESH AIR
 IS CONNETCING TO THE AHU, WHAT'S EXISTING AND WHATS
 NEW, MAKE, SIZE, SEER, BTU'S ETC. OF THE A/C SYSTEMS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, PER 2010
 CITY OF WPB AMEND. 107.2.1.
  
 3) SHOW THE JOB ADDRESS AND A/C CONTRACTOR'S LICENSE ON
 PLAN.
  
 4) PROVE OUT DOOR AIR CALCULATIONS, SEE 2010 FBC/M
 403.3.
  
 5) SHOW COMPLIANCE WITH 2010 FBC/ENERGY 503.2.4.4
 SHUTOFF DAMPER CONTROLS. BOTH OUTDOOR AIR SUPPLY AND
 EXHAUST DUCTS SHALL BE EQUIPPED WITH DAMPERS THAT WILL
 AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES SERVED
 ARE NOT IN USE.
  
 6) COOLING LOAD CAL'S. SUBMITTED APPEAR TO BE A
 RESIDENTIAL PROGRAM BEING USED FOR A COMMERCIAL
 BUILDING APPLICATION, THEY ALSO SHOW THE CEILING HEIGHT
 AT 39.4 FT. THAT WOULD MAKE THIS BUILDING 4 STORIES
 TALL. PLEASE CORRECT PER 2010 CITY OF WPB AMEND. 107.3.
  
 7) COOLING LOAD CAL'S. SHOW THE INFILTRATION AT 54% OF
 HEAT LOADS AND 56% COOLING LOADS, PLEASE EXPLAIN OR
 CORRECT, PER 2010 FBC/ENERGY 503.2.1.
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732
  