| 2012-12-18 15:36:18 | *** CORRETCIONS NEEDED TO MECHANICAL PLANS *** |
| | |
| | 1) EXPLAIN THE USE OF THE BUILDING FOR PROPER PLAN |
| | REVIEW. |
| | |
| | 2) MECHANICAL PLAN SUBMITTED DOES NOT SHOW IF THE AHU'S |
| | ARE HANGING OR ON STANDS WHAT SIZE THE DUCTS ARE, |
| | LOCATION OF RETURN GRILLS, SUPPLY GRILL SIZES, WHERE |
| | THE CONDENSATE LINES DRAIN TO, IF THE CONDENSER UNITS |
| | ARE ON THE ROOF OR SIDE OF BUILDING' HOW THE FRESH AIR |
| | IS CONNETCING TO THE AHU, WHAT'S EXISTING AND WHATS |
| | NEW, MAKE, SIZE, SEER, BTU'S ETC. OF THE A/C SYSTEMS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, PER 2010 |
| | CITY OF WPB AMEND. 107.2.1. |
| | |
| | 3) SHOW THE JOB ADDRESS AND A/C CONTRACTOR'S LICENSE ON |
| | PLAN. |
| | |
| | 4) PROVE OUT DOOR AIR CALCULATIONS, SEE 2010 FBC/M |
| | 403.3. |
| | |
| | 5) SHOW COMPLIANCE WITH 2010 FBC/ENERGY 503.2.4.4 |
| | SHUTOFF DAMPER CONTROLS. BOTH OUTDOOR AIR SUPPLY AND |
| | EXHAUST DUCTS SHALL BE EQUIPPED WITH DAMPERS THAT WILL |
| | AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES SERVED |
| | ARE NOT IN USE. |
| | |
| | 6) COOLING LOAD CAL'S. SUBMITTED APPEAR TO BE A |
| | RESIDENTIAL PROGRAM BEING USED FOR A COMMERCIAL |
| | BUILDING APPLICATION, THEY ALSO SHOW THE CEILING HEIGHT |
| | AT 39.4 FT. THAT WOULD MAKE THIS BUILDING 4 STORIES |
| | TALL. PLEASE CORRECT PER 2010 CITY OF WPB AMEND. 107.3. |
| | |
| | 7) COOLING LOAD CAL'S. SHOW THE INFILTRATION AT 54% OF |
| | HEAT LOADS AND 56% COOLING LOADS, PLEASE EXPLAIN OR |
| | CORRECT, PER 2010 FBC/ENERGY 503.2.1. |
| | |
| | MECHANICAL PLAN REVIEW BY: |
| | TOM GORDON (HY-BYRD INC.) (561) 805-6732 |
| | |