Plan Review Notes
Plan Review Notes For Permit 12120454
Permit Number 12120454
Review Stop B
Sequence Number 1
Notes
Date Text
2012-12-19 14:10:19RESIDENTIAL (R3) REVISION BUILDING REVIEW COMMENTS.
 CODE: 2007 FBC.
  
 1- A) ENTRY DOOR PRODUCT APPROVAL FL11916 SUBMITTED
 DOESN'T MEET THE DESIGN PRESSURES CALCULATED BY THE
 ENGINEER OF RECORD. NEED TO PROVIDE PRODUCT APPROVAL
 THAT MEETS OR EXCEEDS THE CALCULATED DESIGN PRESSURES.
 SEC. R301 OF 2007 FBC-RESIDENTIAL.
  
 B) ENTRY DOOR PRODUCT APPROVAL FL11916 SUBMITTED IS NOT
 LISTED IN THE FLORIDA PRODUCT APPROVAL WEBSITE. PROVIDE
 LISTED PRODUCT APPROVAL. REQUIRED BY DCA RULE 9N-3.
  
 C) ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVAL. SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 2- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF STORM SHUTTERS. SEC. 106.1.1 CITY
 AMENDMENTS TO FBC.
  